2.8.3 DC Input Circuit Breaker

Due to tremendous amounts of short circuit current available (in excess of 1000A for as long as several minutes!)

from bank(s) of batteries, that supply electrical power to inverter systems, it is extremely important to connect a

properly sized DC circuit breaker at the DC input cable that feeds the inverter system. The following table is pro-

vided as a guide for selecting the proper circuit breaker.

Table 2-4: Line To Line Units Suggested DC Circuit Breaker Ratings.

Inverter rating

7 kVA

14 kVA

21 kVA

CB rating

200A

400A

600A

Figure 2-6: Inverter Receiver Junction Box, Input and Output Wiring.

Installation & Operation - Line To Line

3.5 to 21 kVA N+1 Inverter

page 2 — 12

BATTERY

(-)

BATTERY

(+)

JUNCTION

BOX

INVERTER RECEIVER

WITH JUNCTION BOX

BACK VIEW

INVERTER RECEIVER

WITH JUNCTION BOX

SIDE VIEW

GND

L1-IN

L1-OUT

TB1

L2-OUT

L2-IN