Series 90-70 Hot Standby CPU Redundancy User’s Guide – December 1993

GFK-0827

Configuration of a Redundancy Communications Module

As described previously, one Redundancy Communications Module (the Local unit)
must be configured in rack 0 (can be in slots 2 to 9). There must not be an empty slot
between the CPU 780 module and the RCM module. If there is an empty slot, the
configuration will be invalid. The following example screens show an RCM configured
in slot 2 in rack 0. While in the I/O Configuration rack screen, cursor to slot 2 (currently
empty) as shown below.

Select the bem softkey (f3) from the I/O Configuration rack screen, the following screen
will be displayed: