Series 90-70 Hot Standby CPU Redundancy User’s Guide – December 1993

GFK-0827

Following are several examples that illustrate the above guidelines. Each example gives
the role of each unit, its current operating mode, and the state of the LEDs on the RCMs.
An X indicates that the corresponding LED and %S bit is ON.

A. Role switches allowed on both units.

Primary Unit

Secondary Unit

Active

Backup

RUN/ENABLED

RUN/ENABLED

X OK

X OK

X LOC_RDY

X LOC_RDY

X LOC_ACT

LOC_ACT

X REM_RDY

X REM_RDY

REM_ACT

X REM_ACT

B. Role switches allowed on both units.

Primary Unit

Secondary Unit

Active

Backup

RUN/DISABLED

RUN/ENABLED

X OK

X OK

LOC_RDY

X LOC_RDY

X LOC_ACT

LOC_ACT

X REM_RDY

REM_RDY

REM_ACT

X REM_ACT

Note that the Secondary unit drives the outputs in this case.

C. Role switches are not allowed on either unit.

Primary Unit

Secondary Unit

Active

Backup

RUN/ENABLED

RUN/DISABLED

X OK

X OK

X LOC_RDY

LOC_RDY

X LOC_ACT

LOC_ACT

REM_RDY

X REM_RDY

REM_ACT

X REM_ACT

D. Role switches are allowed on both units.

Primary Unit

Secondary Unit

Active

Backup

RUN/DISABLED

RUN/DISABLED

X OK

X OK

LOC_RDY

LOC_RDY

X LOC_ACT

LOC_ACT

REM_RDY

REM_RDY

REM_ACT

X REM_ACT