Siemens MICROMASTER 420 User Manual

Page 138

Advertising
background image

3 Functions

Issue 07/04

MICROMASTER 420 Operating Instructions

138

6SE6400-5AA00-0BP0

Term. 5, 6
or 7

1 k

5, 6
or 7

PNP digital input (P0725 = 1)

Term. 8 (24 V)

Term. 9 (0 V)

Term. 5, 6
or 7

12 k

5, 6
or 7

NPN digital input (P0725 = 0)

Term. 9 (0 V)

Term. 8 (24 V)

R

PTC

900

⇒ DIN switches from "0"

"1"

Fig. 3-58

Connecting a temperature sensor to MICROMASTER 420


NOTE
The specified circuit examples apply for the PTC temperature sensor from the M11
Motor Catalog (motor protection using PTC thermistors, Code Z = A10 – A16) - that
is used for the 1LA and 1LG Siemens motors.

NOTE
In order to avoid noise from being coupled into the drive inverter electronics - with
the associated disturbances - none of the free conductors in the motor cable may
be used to connect the temperature sensor to the drive inverter. The temperature
sensor must be connected to the drive inverter using a separate cable (if possible,
using a shielded cable).

Advertising