Siemens MICROMASTER 420 User Manual

Page 164

Advertising
background image

5 MICROMASTER 420 specifications

Issue 07/04

MICROMASTER 420 Operating Instructions

164

6SE6400-5AA00-0BP0

Input voltage range

3 AC 380 V – 480 V, ± 10 %

(Unfiltered)

Order No.

6SE6420- 2UD13-

7AA1

2UD15-

5AA1

2UD17-

5AA1

2UD21-

1AA1

2UD21-

5AA1

2UD22-

2BA1

2UD23-

0BA1

2UD24-

0BA1

[kW]

0.37 0.55 0.75 1.1

1.5 2.2 3.0 4.0

Output Rating

[hp]

0.5 0.75 1.0 1.5 2.0 3.0 4.0 5.0

Output Power

[kVA]

0.9 1.2 1.6 2.3 3.0 4.5 5.9 7.8

Input Current 1)

[A]

2.2

2.8

3.7

4.9

5.9

8.8

11.1

13.6

Output

Current

[A] 1.2 1.6 2.1 3.0 4.0 5.9 7.7 10.2

Fuse

[A] 10 10 10 10 10 16 16 20

Recommended 3NA 3803 3803 3803 3803 3803 3805 3805 3807

For UL specified

* * * * * * * *

[mm

2

]

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5

Input Cable, min.

[awg]

17 17 17 17 17 17 17 15

[mm

2

]

2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0

Input Cable, max.

[awg]

13 13 13 13 13 9 9 9

[mm

2

]

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Output Cable, min.

[awg]

17 17 17 17 17 17 17 17

[mm

2

]

2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0

Output Cable, max.

[awg]

13 13 13 13 13 9 9 9

[kg]

1.3 1.3 1.3 1.3 1.3 3.3 3.3 3.3

Weight

[lbs]

2.9 2.9 2.9 2.9 2.9 7.3 7.3 7.3

Order No.

6SE6420- 2UD25-

5CA1

2UD27-

5CA1

2UD31-

1CA1

[kW]

5.5 7.5 11.0

Output Rating

[hp]

7.5 10.0 15.0

Output Power

[kVA]

10.1 14.0 19.8

Input Current 1)

[A]

17.3 23.1 33.8

Output Current

[A]

13.2

19.0

26.0

Fuse [A]

20

25

35

Recommended 3NA

3807

3810

3814

For UL specified

* * *

[mm

2

]

2.5 4.0 6.0

Input Cable, min.

[awg]

13 11 9

[mm

2

]

10.0 10.0 10.0

Input Cable, max.

[awg]

7 7 7

[mm

2

]

1.5 2.5 4.0

Output Cable, min.

[awg]

15 13 11

[mm

2

]

10.0 10.0 10.0

Output Cable, max.

[awg]

7 7 7

[kg]

5.5 5.5 5.5

Weight

[lbs]

12.1 12.1 12.1

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 1 % referred to the rated drive converter power and a rated line supply voltage

of 400 V without line commutating reactor. If a line commutating reactor is used, the specified
values are reduced by between 70 % and 80 %.

* UL listed fuses such as Class NON from Bussmann are required for use in America

Advertising