Issue 07/04

5 MICROMASTER 420 specifications

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

163

Input voltage range

3 AC 380 V – 480 V, ± 10 %

(with built in Class A Filter)

Order No.

6SE6420- 2AD22-

2BA1

2AD23-

0BA1

2AD24-

0BA1

2AD25-

5CA1

2AD27-

5CA1

2AD31-

1CA1

[kW]

2.2 3.0 4.0 5.5

7.5 11.0

Output Rating

[hp]

3.0 4.0 5.0 7.5 10.0 15.0

Output Power

[kVA]

4.5 5.9 7.8 10.1 14.0 19.8

Input

Current

1)

[A]

8.8 11.1 13.6 17.3 23.1 33.8

Output

Current

[A]

5.9 7.7 10.2 13.2 19.0 26.0

Fuse

[A] 16 16 20 20 25 35

Recommended 3NA 3805 3805 3807 3807 3810 3814
For UL specified

* * * * * *

[mm

2

]

1.0 1.0 1.5 2.5 4.0 6.0

Input Cable, min.

[awg]

17 17 15 13 11 9

[mm

2

]

6.0 6.0 6.0 10.0 10.0 10.0

Input Cable, max.

[awg]

9 9 9 7 7 7

[mm

2

]

1.0 1.0 1.0 1.5 2.5 4.0

Output Cable, min.

[awg]

17 17 17 15 13 11

[mm

2

]

6.0 6.0 6.0 10.0 10.0 10.0

Output Cable, max.

[awg]

9 9 9 7 7 7

[kg]

3.1 3.3 3.3 5.4 5.7 5.7

Weight

[lbs]

6.8 7.3 7.3 11.9 12.5 12.5

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 1 % referred to the rated drive converter power and a rated line supply voltage

of 400 V without line commutating reactor. If a line commutating reactor is used, the specified
values are reduced by between 70 % and 80 %.

* UL listed fuses such as Class NON from Bussmann are required for use in America