1 uss bus configuration via com link (rs485) – Siemens MICROMASTER 420 User Manual

Page 98

Advertising
background image

3 Functions

Issue 07/04

MICROMASTER 420 Operating Instructions

98

6SE6400-5AA00-0BP0

3.7.1

USS bus configuration via COM link (RS485)

Using MICROMASTER with RS485 communication requires a proper termination
at both ends of the bus (between P+ and N-), and correct pull up/ pull down
resistors at least one end of the bus (e.g. from P+ to P10, and N- to 0 V). (refer to
Fig. 3-30)

Fig. 3-30

RS485 Terminator

When the MICROMASTER drive inverter is the last slave on the bus (refer to Fig.
3-31), and there are no other pull up/pull down resistors on the bus, the supplied
terminator must be connected shown in Fig. 3-30).

First Slave

Last Slave

RS485 Terminator

RS485

Terminator

RS485 Bus

Master

e.g. PLC

Fig. 3-31

USS bus configuration

When the MICROMASTER is the first slave on the bus (refer to Fig. 3-31) the
RS485 Terminator may be used to terminate the bus by using P+ and N- only, for
the bus is powered by the last drive as explained.

NOTE
The supply for the pull up/ pull down resistors must be available whenever RS485
communication is in progress!

Advertising