7 Electro-magnetic compatibility (EMC)

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

171

Class 3: Filtered - for residential, commercial and light industry

This level of performance will allow the manufacturer / assembler to self-certify
compliance of their apparatus with the EMC directive for the residential,
commercial and light industrial environment as regards the EMC performance
characteristics of the power drive system. Performance limits are as specified in
the generic emission and immunity standards EN 50081-1 and EN 50082-1.

Table 7-4

Class 3 - Filtered for Residential, Commercial and Light Industry

EMC Phenomenon

Standard

Level

Emissions:

Radiated Emissions*

EN 55011

Level B

Conducted Emissions

EN 55011

Level B

Immunity:

Supply Voltage Distortion

IEC 1000-2-4
(1993)

Voltage Fluctuations, Dips, Unbalance,
Frequency Variations

IEC 1000-2-1

Magnetic Fields

EN 61000-4-8

50 Hz, 30 A/m

Electrostatic Discharge

EN 61000-4-2

8 kV air discharge

Burst Interference

EN 61000-4-4

2 kV power cables, 2 kV control

Radio Frequency Electromagnetic
Field, amplitude modulated

ENV 50 140

80-1000 MHz, 10 V/m, 80% AM, power
and signal lines

Radio-frequency Electromagnetic Field,
pulse modulated

ENV 50 204

900 MHz, 10 V/m 50% duty cycle, 200 Hz
repetition rate


* These limits are dependent on the inverter being correctly installed inside a

metallic switchgear enclosure. The limits will not be met if the inverter is not
enclosed.


NOTICE

To achieve these performance levels, you must not exceed the default Pulse
frequency nor use cables longer than 25 m.

The MICROMASTER inverters are intended exclusively for professional
applications

. Therefore, they do not fall within the scope of the harmonics

emissions specification EN 61000-3-2.

Maximum mains supply voltage when filters are fitted is 460 V.