Soleus Air KFHHP-22 User Manual

Page 29

Advertising
background image

Improper setting of temperature

Whether cooling (heating) load
is proper

Adjust the set temperature

Check the estimated load of cooling (heating)

Leakage or shortage of refrigerant

Leakage occurs between high and
low pressure inside compressor

Malfunction of four-way valve

Partial blockage of capillary

Blockage of cooling system

Replace the compressor

Replace the four-way valve

Replace the capillary

Use the method of observing condensation
on the evaporator and pressure value of
high pressure manometer to see whether
the system is blocked and carry out
corresponding handling on the system

Vacuumize after leakage detection
and leakage repair. Charge refrigerant
according to specification.

Malfunction of
refrigerant flow

Poor thermal insulation of connecting
pipe of indoor and outdoor unit

Ensure that both thick pipe and thin pipe are insulated
well. The exposed part of the connector and copper pipe
must be insulated as well.

Heat exchanger of outdoor unit
is blocked

Air filters are blocked

Fan speed is set too slow

Fan speed turns low

Improper installation location
for outdoor unit

Outdoor unit should be installed in a

place with well ventilation

Set the fan speed to high or medium
speed

Clean the filter

Clean the dust accumulated on the
surface of the heat exchanger

Air circulation
is insufficient

Damage of

capacitor

damaged

Damage of

motor

Replace the

capacitor

Replace the motor

Flashing or awning can be installed appropriately. If the

max. cooling capacity cannot be satisfied, replacement of

the air conditioner is recommended.

Maintain a certain degree of indoor sealability. Try not to
use appliance with high amount of heat.

Outdoor temperature is too high

Indoor sealability is inadequate; too many
people go in and out frequently; there is
heating unit in the room.

Poor cooling

(heating) effect

2

9