water leakage

drain hose is blocked or broken

replace the drain hose

wrap and tight it again

adjust the location of fan

abnormal things in indoor unit

remove it

compresoor shakes overly

pipes in outdoor unit collides

set the pipes apart

adjust the washer and tight the bolt

metal plates collides

tighten the connecting bolt

indoor fan collides with other parts

outdoor fan collides with case

adjust the fan location

abnormal sound inside compressor

replace compressor

abnormal electromagnetic sound in

short circuit inside electromagnetic valve;repalace it

4-way valve in HEAT mode

stick shake-reduction plaster between the metal plates

CAUTION:

1,When repairing,before the voltage between module PN is measured below 50V,do not touch any terminal

to avoid electrical shock

2,When replacing power module and rectifier,make sure to spread the indicating paste evenly

abnormal shake

or sound

-30-

connector of refrigerant pipe isn't wrapped well