Siemens Albatros Zone Controler CE1U2353en01a User Manual

Page 11

Advertising
background image

11/26

Siemens Schweiz AG

User Manual OEM

CE1U2353en01a

HVAC Products

Overview of OEM settings 22.

November

2006

Operating line

User level

Function

Default value

Minimum

Max

Unit

5950 I Function

input

H1

Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Excess
heat discharge

Optg mode change
HCs+DHW

-

5951 I

Contact type H1

NC ¦ NO

NO contact

-

5952 I

Min flow temp setpoint H1

70

8

120

°C

5954 I

Heat request 10V H1

100

5

130

°C

5956 I

Pressure value 3.5V H1

5.0

0.0

10.0

bar

5960 I Function

input

H2

Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦ Heat
generation lock ¦ Error/alarm message ¦ Min flow temp
setpoint ¦ Heat request ¦ Pressure measurement

Optg mode change
HCs+DHW

-

5961 I

Contact type H2

NC ¦ NO

NO contact

-

5962 I

Min flow temp setpoint H2

70

8

120

°C

6014 I

Function mixing group 1

Heating circuit ¦ Prim contr/system pump

Heating circuit

-

6020 I

Function extension module 1

None ¦ Multi-functional ¦ Heating circuit ¦ Solar DHW ¦
Prim contr/system pump

No function

-

6021 I

Function extension module 2

None ¦ Multi-functional ¦ Heating circuit ¦ Solar DHW ¦
Prim contr/system pump

No function

-

6097 F Sensor type collector

NTC 10k ¦ Platinum 1000

NTC

6030 I Relay

output

QX21

None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
Q20 ¦ H2 pump ¦ Q18 primary pump Q14

None

-

6031 I Relay

output

QX22

None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
Q20 ¦ H2 pump ¦ Q18 primary pump Q14

None

-

6040 I Sensor

input

Bx21

None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39

None

-

6041 I Sensor

input

BX22

None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39

None

-

6097 Sensor type collector

NTC 10k ¦ Platinum 1000

NTC

6098 F Readjustm collector sensor

0

-20

20

°C

6100 F Readjustm outside sensor

0.0

-3.0

3.0

°C

6110 F Time

constant

building

15

0

50

h

6112 O Gradient room model

60

0

300

min/°C

6120 F Frost protection plant

Off ¦ On

On

-

6200 I Saving

sensors

No ¦ Yes

No

-

Advertising