HVAC Products

Overview of OEM settings 22.

November

2006

Operating line

User level

Function

Default value

Minimum

Max

Unit

1630 I

Charging priority

Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute

MC shifting, PC absolute

-

1640 F Legionella

function

Off ¦ Periodically ¦ Fixed weekday

Fixed weekday

-

1641 F Legionella funct periodically

3

1

7

Days

1642 F Legionella funct weekday

Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦
Saturday ¦ Sunday

Montag

1644 F Legionella funct time

− − −

− − − / 00:00

23:50

hh:mm

1645 F Legionella funct setpoint

65

55

95

°C

1646 F Legionella funct duration

30

− − − / 10

360

min

1647 F Legionella funct circ pump

Off ¦ On

On

-

1660 F Release of the circulating pump

Time program 3/HCP ¦ DHW release ¦ Time program
4/DHW

DHW release

-

1661 F Circulating pump cycling

Off ¦ On

On

-

1663 F Circulaton

setpoint

45

8

80

°C

Pump H1/H2
2008 O H1 DHW charging priority

No ¦ Yes

Yes

2010 F H1 Excess heat draw

Off ¦ On

On

2014 F H1 prim contr/system pump

No ¦ Yes

Yes

-

2033 O H2 DHW charging priority

No ¦ Yes

Yes

2035 F H2 Excess heat draw

Off ¦ On

On

2039 F H2 prim contr/system pump

No ¦ Yes

Yes

-

Primary controller / system pump

2110 O Flow temp setpoint min

8

8

95

°C

2111 O Flow temp setpoint max

80

8

95

°C

2130 O Mixing valve boost

10

0

50

°C

2132 O Actuator:type

2-position ¦ 3-position

3-position

2133 O Switching differential 2-pos

2

0

20

°C

2134 O Actuator:

running

time

120

30

873

°C

2135 O Mixing

valve

Xp

32

1

100

°C

2136 O Mixing valve Tn

120

10

873

°C

Solar
3810 F Temp diff on

8

BZ 3811

40

°C

3811 F Temp diff off

4

0

BZ 3812

°C

3812 F Charg temp min DHW st tank

− − −

− − − / 8

95

°C

3830 F Collector start function

− − −

− − − / 5

60

min

3831 F Min run time collector pump

60

5

120

s

3840 F Collector frost protection

− − −

− − − / -20

5

°C

3850 F Collector overtemp prot

− − −

− − − / 30

200

°C

3860 F Evaporation heat carrier

− − −

− − − / 60

200

°C

Advertising