Siemens Albatros Zone Controler CE1U2353en01a User Manual

Page 8

Advertising
background image

8/26

Siemens Schweiz AG

User Manual OEM

CE1U2353en01a

HVAC Products

Overview of OEM settings 22.

November

2006

Operating line

User level

Function

Default value

Minimum

Max

Unit

1151 F Floor curing setp manually

25

0

95

°C

1161 F Excess heat draw

Off ¦ Heating mode ¦ Always

Always

1172 F With prim contr/system pump

No ¦ Yes

Yes

1200 I Optg

mode

changeover

Protection ¦ Recuced

Protection

Heating circuit P
1300 E Operating

mode

Protection ¦ Automatic ¦ Reduced ¦ Comfort

Automatic

-

1310 E Comfort cooling setpoint

20.0

BZ 1012

BZ 1016

°C

1312 E Reduced setpoint

16

BZ 1014

BZ 1010

°C

1314 E Frost protection setpoint

10.0

4

BZ 1012

°C

1316 F Comfort setpoint max

35.0

BZ 1010

35

°C

1320 E Heating

curve

slope

1.50 0.10

4.00

-

1321 F Heating

curve

displacement

0.0

-4.5

4.5

°C

1326 F Heating

curve

adaption

Off ¦ On

Off

-

1330 E Summer/winter

heating

limit

18

− − − / 8

30

°C

1332 F 24-hour heating limit

-3

− − − / -10

10

°C

1340 F Flow temp setpoint min

8

8

BZ 1041

°C

1341 F Flow temp setpoint max

80

BZ 1040

95

°C

1350 F Room influence

20

− − − / 0

100

%

1360 F Room temp limitation

− − −

− − − / 0.5

4

°C

1370 F Boost

heating

5

− − − / 0

20

°C

1380 F Quick

setback

Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint

Down to reduced setpoint

-

1390 F Optimum start control max

0

0

360 min

1391 F Optimum stop control max

0

0

360 min

1400 F Reduced

setp

increase

start

− − −

− − − / -30

10

°C

1401 F Reduced setp increase end

-15

-30

BZ 1100

°C

1420 F Overtemp prot pump circuit

Off ¦ On

On

-

1450 I

Floor curing function

Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually

Off

-

1451 I

Floor curing setp manually

25

0

95

°C

1455 F Floor curing setp current

0

0

95

°C

1456 F Floor curing day current

0

0

32

°C

1461 F Excess heat draw

Off ¦ Heating mode ¦ Always

Always

1172 F With prim contr/system pump

No ¦ Yes

Yes

1500 I Optg

mode

changeover

Protection ¦ Recuced

Protection

Domestic hot water
1610 E Nominal setpoint

55

BZ 1612

BZ 1614 OEM

°C

1612 F Reduced setpoint

40

8

BZ 1610

°C

1614 O Nominal

setpoint

max

65

8

80

°C

1620 I Release

24h/day ¦ Time programs HCs ¦ Time program 4/DHW

Time programs HCs

-