2 the settings in detail, 2 heating circuits – Siemens Albatros Zone Controler CE1U2353en01a User Manual

Page 15

Advertising
background image

15/26

Siemens Schweiz AG

User Manual OEM

CE1U2353en01a

HVAC Products

The settings in detail 22.

November

2006

2 The settings in detail

2.1 Operator

section

Operation and display

Line no.

Operating line

30 Data:read

No
Yes

31 Data:write

No
Yes


The setting data of all operating levels are copied from the controller to the memory of
the operator unit. This means that previous data in the operator unit will be overwritten.

With the exception of the data listed below, the setting data of all operating levels are
transferred from the memory of the operator unit to the connected controller. Previous
setting data in the controller will be overwritten.

The following data will not be overwritten:

Line no.

Operating line

3

Year

130

Room unit 1

131

Room unit 2

132

Outside sensor

133

Repeater

134

Operator unit

135

Service unit

138

Delete all devices

516

default values

536

default values

556

default values

576

default values

6222 Device

hours

run

6600 device

address

6601 Segment

address

6650 Outside

temp

source


2.2 Heating

circuits

mixing valve control

Line no.

Operating line

HC1 HC2 HC3P

835 1135

Mixing

valve

Xp

836 1136

Mixing

valve

Tn


The proportional band defines within which change of the control variable

∆x (∆T of the

flow) the whole correcting span y (valve travel) is traversed.
The smaller the proportional band, the greater the change of the manipulated variable
∆y at a given change of the controlled variable ∆x.

The integral action time is the period of time the controller’s I-part would require to
produce the same change of the manipulated variable as the P-part

Data:read

Data:write

Mixing valve Xp

Mixing valve Tn

Advertising