8 lpb – Siemens Albatros Zone Controler CE1U2353en01a User Manual

Page 22

Advertising
background image

22/26

Siemens Schweiz AG

User Manual OEM

CE1U2353en01a

HVAC Products

The settings in detail 22.

November

2006

The setting is used to calculate the fictive room temperature of rooms that have no
room temperature sensor installed (operating lines 8742, 8772, and 8802).

Parameters

Line no.

Operating line

6204 Save

parameters

.
The current parameter settings can be saved as new standard settings. Exempted from
this are the following operating pages: Time of day and date, operator section, wireless,
and all time programs, as well as the number of operating hours and the different
counters.
Important:
With this process, the factory settings will be overwritten and can no longer be
retrieved!

Line no.

Operating line

6222

Device hours run


This indicates the total number of operating hours since the controller was first
commissioned.

2.8 LPB

Error / maintenance / alarms

Line no.

Operating line

6610

Display system messages

6612 Alarm

delay

6620

Action changeover functions

Segment
System


This setting enables system messages transmitted via LPB to be suppressed at the
connected operator unit.


Delivery of the alarm to the OCI can be delayed in the basic unit by setting a delay.
This ensures that unnecessary notifications of a service center resulting from short-time
errors (e.g. temperature limiter cut out, communication error) can be prevented.
It is to be noted, however, that errors occurring for a short period of time, and
reoccurring constantly and rapidly, will also be filtered.

Range of action of changeover

The range of action of central changeover can be defined.
This applies to the following types of limitation:
• Optg mode changeover
• Summer changeover (when selecting ”Central“ on setting line 6621)
Entries:
• Segment: Changeover takes place with all controllers in the same segment.
• System: Changeover takes place with all controllers in the entire system (in all

segments). The controller must be located in segment 0!

Device hours run

Display system messages

Alarm delay