The settings in detail 22.

November

2006

An adjustment of the integral action time changes the valve’s rate of response.
The longer the integral action time Tn, the slower the response of the controlled
system.

239

2

Z

08

Tn

y

t

Xp

1

t

x

@

2.3 Domestic hot water

Setpoints

Line no.

Operating line

1614

Nominal setpoint max


This operating line is used to limit the “Nominal setpoint“ (operating line 1610) at the
top.

Release

Line no.

Operating line

1620 Release

24h/day
Time programs HCs
Time program 4 / DHW


24h/day
The DHW temperature is constantly maintained at the nominal DHW setpoint,
independent of any time programs.

Example:


Time programs HCs
The DHW setpoint is switched between the nominal DHW setpoint and the reduced
DHW setpoint according to the heating circuits’ time programs. The first switch-on point
of each period is shifted forward in time by one hour.

0

6

12

18

24

h

23

71

Z1

8