Siemens Schweiz AG

User Manual OEM

CE1U2353en01a

HVAC Products

Overview of OEM settings 22.

November

2006

Operating line

User level

Function

Default value

Minimum

Max

Unit

832 F Actuator:type

2-position ¦ 3-position

3-position -

833

F Switching differential 2-pos

2

0

20

°C

834

F Actuator:

running

time

120

30

873

s

835 O

Mixing

valve

Xp

32

1

100

°C

836

O Mixing valve Tn

120

10

873

s

850

I

Floor curing function

Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually

Off

-

851

I

Floor curing setp manually

25

0

95

°C

861

F Excess heat draw

Off ¦ Heating mode ¦ Always

Always

872

F With prim contr/system pump

No ¦ Yes

Yes

900 I Optg

mode

changeover

Protection ¦ Recuced

Protection

Heating circuit 2
1010 E Comfort cooling setpoint

20.0

BZ 1012

BZ 1016

°C

1012 E Reduced setpoint

16

BZ 1014

BZ 1010

°C

1014 E Frost protection setpoint

10.0

4

BZ 1012

°C

1016 F Comfort setpoint max

35.0

BZ 1010

35

°C

1020 E Heating curve slope

1.50

0.10

4.00

-

1021 F Heating curve displacement

0.0

-4.5

4.5

°C

1026 F Heating curve adaption

Off ¦ On

Off

-

1030 E Summer/winter heating limit

18

− − − / 8

30

°C

1032 F 24-hour heating limit

-3

− − − / -10

10

°C

1040 I

Flow temp setpoint min

8

8

BZ 1041

°C

1041 I

Flow temp setpoint max

80

BZ 1040

95

°C

1050 F Room influence

20

− − − / 0

100

%

1060 F Room temp limitation

− − −

− − − / 0.5

4

°C

1070 F Boost

heating

5

− − − / 0

20

°C

1080 F Quick setback

Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint

Down to reduced setpoint

-

1090 F Optimum start control max

0

0

360 min

1091 F Optimum stop control max

0

0

360 min

1100 F Reduced setp increase start

− − −

− − − / -30

10

°C

1101 F Reduced setp increase end

-15

-30 BZ

1100

°C

1120 F Overtemp prot pump circuit

Off ¦ On

On

-

1130 F Mixing valve boost

10

0

50

°C

1132 F Actuator:type

2-position ¦ 3-position

3-position -

1133 F Switching differential 2-pos

2

0

20

°C

1134 F Actuator:

running

time

120

30

873

s

1135 O Mixing

valve

Xp

32

1

100

°C

1136 O Mixing valve Tn

120

10

873

s

1150 F Floor curing function

Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually

Off

-