Preset multiple registers” command \(16#10\), Modbus protocol exception responses, Appendix f: modbus commands – Schneider Electric Gateway LUFP7 User Manual

Page 109

Advertising
background image

110

13. Appendix F: Modbus Commands

Chapter 6.11 Adding and Setting Up a Modbus Command, page 68, also shows a few examples of
correspondences between the elements displayed in AbcConf and the corresponding Modbus frame fields.

See also:

Chapter 6.11.2 With a Generic Modbus Slave, page 70, and chapter 6.11.3 Adding a Special Modbus

Command, page 80, if the implementation of one of these commands would be incompatible with its
implementation in the gateway, for example. You then have to create a special Modbus command to
compensate for this incompatibility.

N.B.

here, the notions of “input” and “output” (and assimilated) are irrelevant, as all Modbus commands have

access to all of a Modbus slave’s memory. However, these names are retained in order to comply with the terms
used in the standard Modbus documentation.

13.1. “Read Holding Registers” Command (16#03)

Frame

Field

Value or properties

Query

Starting Address (MSB)
Starting Address (LSB)

- Address of the 1st output / internal register

Number of points (PF)
Number of points (Pf)

- Number of output / internal registers

Response

Byte count

- Number of data bytes = Number of output / internal registers × 2

Data (first register / MSB)
Data (premier registre / Pf)

………

Data (dernier registre / PF)
Data (dernier registre / Pf)

- Byte swap = “No swapping” (or “Swap 2 bytes”)

- Data length = Value of the “Byte count” field

- Data location = Address in the gateway’s input memory

13.2. “Preset Single Register” Command (16#06)

Frame

Field

Value or properties

Query

Register (MSB)
Register (LSB)

- Address of the output / internal register

Preset data (MSB)

Preset data (LSB)

- Byte swap = “No swapping” (or “Swap 2 bytes”)
- Data length = 16#0002
- Data location = Address in the gateway’s output memory

Response

Register (MSB)
Register (LSB)
Preset data (MSB)
Preset data (LSB)

- Byte swap = “No swapping” (or “Swap 2 bytes”)
- Data length = 16#0002
- Data location = Address in the gateway’s input memory
N.B.:

These data are an echo to the query. So in most cases there is no

need to feed them back to the Profibus-DP master.

Instead of creating a link between the echo of the response to the “Preset Single Register”
Command (16#06) and the memory area dedicated to the Profibus-DP inputs (16#0002-
16#00F3), you’d better link it with the address 16#0400.