7. Appendix A: Technical Characteristics

Profibus-DP
characteristics
(cont'd)

• Maximum number of stations: 32 stations per segment, repeater included; up to

126 stations with all three repeaters (repeaters included). Address 126 is reserved
and should therefore not be used for exchanging data.

• Possible types of stations: there are three types of Profibus-DP stations:

- Class 1 DP master (DPM1): PLC, PC, etc. exchanging information with DP slaves.
- Class 2 DP master (DPM2): A programming, bus configurating, or commissionning

device, used to configure the Profibus-DP network upon commissioning and operation,
or supervision.

- DP slave: Peripheral device that exchanges data cyclically with “its” active DPM1

station.

• Mono-master or multi-master network.
• Hybrid access method: Acyclical communication between masters using the

transfer of a token (synchronisation); cyclical master/slaves communications
(application data transfers).

• Up to 244 input bytes and 244 output bytes per DP slave; typical exchange of

32 bytes per slave.

• Operating modes: Functional operations (cyclical I/O exchanges), resetting to

zero (input reading and output resetting), or disruption (only inter-master
functions are allowed).

• Input (Freeze-Mode) and/or output (Sync-Mode) synchronisation of all DP

slaves.

• Other services offered:

- Verification of DP slaves configuration.
- Advanced diagnostics on three hierarchical levels.
- Allocation of DP slaves addresses.
- DP slaves provided with a watchdog triggering timeout.
- Protection of DP slaves' access to I/O.

• Possibility to connect or disconnect a station without impacting on

communications between other stations.

• Performance

results:

diagram

presenting the bus
cycle time of a mono-
master Profibus-DP
network, according to
the number of DP
slaves present on
that network (with 2
input bytes and 2
output bytes per DP
slave).

Test conditions: minimum slave time interval = 200 µs; TSDI = 37 × duration of
one bit; TSDR = 11 × duration of one bit.

Profibus-DP LUFP7
gateway specifics

• Network type: PROFIBUS EN 50 170 (DIN 19245).
• Protocol version: v1.10.
• Standard connections: Female SUB-D 9-point connector, which is

recommended for baud rates exceeding 1.5 Mbits/s.

• All baud rates supported (9.6, 19.2, 93.75, 187.5, 500, 1,500, 3,000, 6,000 and

12,000 kbits/s); automatic baud rate detection.

• "DP slave" Profibus-DP station.
• Cyclical data transmissions: up to 244 input bytes and 244 output bytes;

416 bytes exchanged maximum, inputs and outputs included; 24 modules
maximum used to configure these I/O.