Appendix b: lufp7 gateway gsd file – Schneider Electric Gateway LUFP7 User Manual

Page 90

Advertising
background image

91

8. Appendix B: LUFP7 Gateway GSD File

The LUFP7 gateway GSD file contains all the information and settings for configuring the gateway under
Profibus-DP. This file, “Tele071F.gsd”, is used by SyCon to generate information that will eventually be used

by the DPM1 master PLC during setup phases.

Refer to chapter 4.2.4 Setting up the Gateway Description Files, page 28, to review the procedure for importing
the GSD file under SyCon.

8.1. Identification Number

The most important information contained in the GSD file is the identification number “

Ident_Number

” of the

device type it designates (DP slave or DPM1 master). This identification number is, in particular, used by a
DPM1 master upon setting up its communications with a DP slave, in addition to checking its address on the
Profibus-DP network.

The allocation of Profibus-DP identification numbers is reserved for the Profibus International (PI) association. As
each identification number is unique and specific to each device type, you should change neither the number, nor
the remainder of the provided GSD file. Schneider Electric reserves the rights to change the content of this file.

Sample Profibus-DP products, with their identification numbers and the related GSD files:

Schneider Electric product

Identification number

Name of the related GSD file

LUFP7 gateway

16#071F

Tele071F.gsd

T

EGO

P

OWER

16#BECE

tk3110.gsd

ATV58

16#00B9

Tele00b9.gsd

ATV68

16#1234

VEE_1234.gsd

TSX PBY 100

16#1654

Sad_1654.gsd

ATV58/ATV66 gateway

16#2332

atvp2332.gsd

8.2. GSD File Content

;============================================================
; Profibus Device Database of :
; Schneider Electric Gateways
; Model : LUFP7
; Description : Profibus-DP/Modbus Gateway
; Language : English
; Date : 14 November 2002
; Author : Schneider Electric [EB/JFR]
;============================================================
#Profibus_DP

GSD_Revision = 2

GSD file header.

; Device identification
Vendor_Name = "Schneider Electric"
Model_Name = "LUFP7"
Revision = "Version 1.0"
Ident_Number = 0x071F
Protocol_Ident = 0 ; DP protocol
Station_Type = 0 ; Slave device
FMS_supp = 0 ; FMS not supported
Hardware_Release = "Version 1.41"
Software_Release = "Version 1.12"

LUFP7 gateway identification as a
Profibus-DP device.

Advertising