13. Appendix F: Modbus Commands

13.3. “Preset Multiple Registers” Command (16#10)

Frame

Field

Value or properties

Query

Starting Address (MSB)
Starting Address (LSB)

- Address of the 1st output / internal register

Number of Registers (MSB)
Number of Registers (LSB)

- Number of output / internal registers

Byte Count

- Number of data bytes = number of output / internal registers × 2

Data (first register / MSB)
Data (first register / LSB)

………

Data (last register / MSB)
Data (last register / LSB)

- Byte swap = “No swapping” (or “Swap 2 bytes”)

- Data length = Value of the “Byte count” field

- Data location = Address in the gateway’s output memory

Response

Starting Address (MSB)
Starting Address (LSB)

- Address of the 1st output / internal register

Number of Registers (MSB)
Number of Registers (LSB)

- Number of output / internal registers

13.4. Modbus Protocol Exception Responses

When it cannot process a command dictated by a Modbus query, a slave sends an exception response instead
of the normal response to the query.

With standard Modbus commands, the LUFP7 gateway considers that all exception responses
which it receives from Modbus slaves are incorrect responses. As a result, it will carry out the
re-transmissions configured for the queries involved.

If you want the software application for your Profibus-DP master to be able to specifically
manage exception responses, you can replace the Modbus command, in AbcConf, with a
personalized command (see chapter 6.11.3.2 Modbus Commands which Can Be Completely
Changed by the User, page 80). This then allows you to feed back the “Slave Address” and
“Function” fields to the Profibus-DP master.

The structure of an exception response is independent of the Modbus command associated with the “Function”
field of the query involved. The whole frame of an exception response is shown below :

Slave Address

Modbus address (1 to 247; addresses 125, 126 and 127 prohibited): The value of this field
is identical to that of the “Slave Address” field of the query involved.

Function

Command code, with exception indicator: The value of this field is set to 16#80 + the value
of the “Function” field of the query involved.

Exception Code

Code indicating the nature of the error which has caused the exception response (see table
on next page).

Checksum (Lo)

Checksum (Hi)

Error check