Software implementation of the gateway – Schneider Electric Gateway LUFP7 User Manual

Page 30

Advertising
background image

31

4. Software Implementation of the Gateway

• In the “Assigned master” frame, check that the Profibus-DP master previously configured is selected. If not,

select it. N.B. Only the "Assigned master" can control the DP slave to which it has been allocated during the
configuration phase. Other DPM1 masters can only read its I/O values.

• In the "General" frame, verify that the two boxes "Activate device in actual configuration" and "Enable

watchdog control" are both checked. If not, please check both.

• Validate the operations conducted by clicking on “OK”.

The left-hand

portion of this area

specifies the

gateway's

maximum capacity,

whilst the right-

hand portion lists

the currently

configured

"Modules".

N.B. Don't use the “Symbolic Names” option to name the I/O exchanged with the gateway. This operation is
useless because the symbols you shall define under SySon would not be exported and retrieved under
PL7 PRO!

If you create or edit a configuration using AbcConf (see chapter 6 Configuring the Gateway,
page 44), you should be aware that the total size of the inputs and outputs, for all the
configured modules, should be identical to the size of the data configured under AbcConf.
They correspond to all the bytes exchanged with the Modbus slaves via the “Data” fields of the
Modbus frames, to the two words reserved for downstream Modbus network management
(see chapter 5 Gateway Initialization and Diagnostics, page 37), if it has not been disabled,
and also to the two read parameter read/write counters . Any “free memory location” inserted
between two data elements, regardless of its size, is included in the bytes exchanged.

N.B. If the "Length of input data" or the "Length of output data" configured for the gateway
(under SyCon) differs from the total size of the gateway input memory area or the total size of
the gateway output memory area (under AbcConf), the gateway shall refuse going on line
(LED

n

off and LED

o

red) and the configuration error shall be indicated (LED

q

flashing

red, at 1 Hz). Please see chapter 3 Signalling, page 23.