Sharp JW-21MN User Manual

Page 56

Advertising
background image

11-3

4

3

2

1

0

F E

D

C

B A

9

8

7

6

5

(Factory setting: OFF)

ON
OFF

LT

(Rear side)

(4) Termination resistance switch (LT)

When the JW-21MN is at the termination station of the communication line, make sure to set the
termination resistance switch to "ON."

(Factory setting: 00)

(Front side)

1

23

4

5

6

7 8 9

0

1

23

4

5

6

7 8 9

0

1

10

STA NO.

STA NO.

(3) Station number switch (STA NO.)

Make sure to set the master station number to "00." For slave stations, set from "01" to "77" in
octagonal sequence.

ON

OFF

Setting

Condition of the JW-21MN

Insert a termination resistance

Do not insert a termination resistance

- Maximum amount of slave stations to be connected are

63. As the station number should be assigned by
octagonal figures, setting of the following values causes
errors and the JW-21MN cannot communicate.
08, 09, 18, 19, 28, 29, 38, 39, 48, 49, 58, 59, 68, 69, and
78 to 99.

- Be careful that there is no doubly allocated number and no

number has been skipped.

- When using a termination (ME-75 made by Toko

Denshi) (device to function as terminator) at the end
of a signal cable, turn "OFF" the termination resis-
tance switch of the termination station.

Reference

Need for the termination resistance

When a termination resistance is not provided at a communication circuit end, the end of the circuit
generates reflection waves. These reflection waves collide with sending signals and abnormal
communication may occur. The termination resistance prevents the occurrence of these reflection
waves. On the other hand, when an intermediate station has its termination resistance switch turned
"ON," this station causes reflection and attenuates signals and causes abnormal communication.

Termination

(ME-75)

Termination

Termination

1 km max.