Power-limited Wiring Requirements

2. Installation

PDRP-1001 Instruction Manual PN 50734:D0 04/06/01

17

Observe polarity when connecting the batteries. Connect the battery cable (p/n 75203 or 75202, depending
on terminal size of battery) to terminal J9 on the main circuit board using the plug-in connector provided.
Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing batteries.
Do NOT connect battery interconnect wire at this time.

Figure 5 Battery Installation and Connection

Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-
limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any nonpower-limited circuit
wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must pass
through separate knockouts and/or conduits.

Figure 6 Power-limited Wiring Requirements

J3

J9

J2

AMP

TB5

MS

44

-B

A

Tc

onn

.c

dr

GEN
ALM2

TONE

SILENCE

ALARM

SILENCE

ALARM

ACTIVATE

SYSTEM

RESET

AC POWER

SYSTEM

ALARM

ALARM T EST

SUPERVISORY

SYSTEM

TROUBLE

CIRCUIT

TROUBLE

ALARM

SILENCED

POWER

TROUBLE

ZONE 1

ZONE 2

ZONE 3

ZONE 4

SW1

TB1

TB2 TB3

TB4

JP1

SUPV 1

SUPR 2

GEN
ALM1

J4

J5

J7

J8

OPT1

OPT2

J10

J3

J9

J2

AMP

J1

TB5

OUT#1

B+ A+ A– B–

OUT#3

B+ B–

OUT#4

B+ B–

ALARM

NO NC C

OUT#2

B+ A+ A– B–

IN #1

B+ A+ A– B–

IN #2

B+ A+ A– B–

IN #3

B+ A+ A– B–

IN #4

B+ A+ A– B–

TB1

LATCH

DISABLE

J2

TB1

TBL

J1

J2

7

6

5

1

PO

W

ER

L

IM

IT

ED

AC Power

MRP

44

-p

lwiri

ng

.cdr

Power-limited
Circuits

Nonpower-limited
Circuits

Power-limited Circuits

Nonpower-limited
Circuits

Power-limited

Circuits

Advertising