Setting mode of operation, Basic program – System Sensor PDRP-1001 User Manual

Page 28

Advertising
background image

2. Installation

Setting Mode of Operation

28

PDRP-1001 Instruction Manual PN 50734:D0 04/06/01

Setting Mode of Operation

Select operating mode by setting the SW1 DIP switches as described below.

After any changes are made to the configuration of the switches, the panel must be reset.

For Canadian use, refer to "Sprinkler Supervisory Tracking" on page 34.

Figure 19 DIP Switch Settings

Basic Program

Select the desired mode of operation and set DIP Switches 1 and 2 per the appropriate column.

Note: Output 1 and 2 refer to Notification Appliance Circuits; Output 3 and 4 refer to Releasing Circuits.

Mode 1

Two Zone

Single Hazard

Mode 2

Cross Zone

Single Hazard

Mode 3

Combined Release

Dual Hazard

Mode 4

Split Release
Dual Hazard

Switch 1
Switch 2

OFF
OFF

ON

OFF

OFF

ON

ON
ON

Output 1 & 3 -
Activated by an
alarm on either IDC
1 or 2.
Output 2 -
Activated by a
waterflow alarm on
IDC 3.
Output 4 -
Activated by a
supervisory condition
on IDC 4.

Output 1 -
Activated by an
alarm on either IDC
1 or 2.
Output 2 -
Activated by a
waterflow alarm on
IDC 3.
Output 3 -
Activated by alarms
on both IDC 1 and 2.
Output 4 -
Activated by a
supervisory condition
on IDC 4.

Output 1 -
Activated by an
alarm on either IDC
1 or 2 or a waterflow
alarm on IDC 3.
Output 2 -
Activated by a
supervisory condition
on IDC 4.
Output 3 & 4 -
Activated by an
alarm on either IDC
1 or 2.

Output 1 -
Activated by an
alarm on either IDC
1 or 2 or a waterflow
alarm on IDC 3.
Output 2 -
Activated by a
supervisory condition
on IDC 4.
Output 3 -
Activated by an
alarm on IDC 1.
Output 4 -
Activated by an
alarm on IDC 2.

SW1

MS

44

-d

ipsw

.c

dr

Basic Programming

Switch 1: Cross Zone

Switch 2: Dual Hazard

Discharge Timer
Switch 3: Discharge Timer
Switch 4: Discharge Timer
Switch 5: Discharge Timer

Not Used