Appendix B: Compatible Devices

Two-wire Smoke Detectors, UL Listed

Use the two-wire detectors listed below.

Table 3 Two-wire Smoke Detectors

Detector
Model

Identifier

Type

Base

Model

Identifier

Standby

Current

(mA)

Detectors

per Zone

System Sensor 1400

A

Ionization

n/a

n/a

0.10

20

System Sensor 1451

A

Ionization

B401/B401B/

B406B

A

0.12

15/15/1

System Sensor 1851DH

A

Ionization

DH1851DC

A

0.12

15

System Sensor 2400

A

Photoelectric

n/a

n/a

0.12

15

System Sensor 2400AIT

A

Photo/

Isolated

Thermal/Horn

n/a

n/a

0.12

15

System Sensor 2400AT

A

Photo/

Thermal/Horn

n/a

n/a

0.12

15

System Sensor 2400TH

A

Photo/

Thermal

n/a

n/a

0.12

15

System Sensor 2451

A

Photoelectric B401/B401B/

B406B

A

0.12

15/15/1

System Sensor 2451TH

A

Photo/

Thermal

B401/B401B/

B406B

A

0.12

15/15/1

System Sensor 2851DH

A

Photoelectric

DH2851DC

A

0.12

15

System Sensor 1451DH

A

Ionization

DH400

A

0.12

15

System Sensor 2451

A

Photoelectric

DH400

A

0.12

15

System Sensor 2300T

A

Photo/

Thermal

n/a

n/a

0.12

15

System Sensor 1800

A

Ionization

n/a

n/a

0.12

n/a

System Sensor 1851B

A

Ionization

B101B

A

0.12

n/a

System Sensor 1851B

A

Ionization

B107B

A

0.12

n/a

System Sensor 2800

A

Photoelectric

n/a

n/a

0.12

n/a

System Sensor 2800TH

A

Photo/

Thermal

n/a

n/a

0.12

n/a

System Sensor 2851B

A

Photoelectric

B101B

A

0.12

n/a

System Sensor 2851B

A

Photoelectric

B107B

A

0.12

n/a

System Sensor 2851BTH

A

Photo/

Thermal

B101B

A

0.12

n/a

System Sensor 2851BTH

A

Photo/

Thermal

B107B

A

0.12

n/a

System Sensor 1151

A

Ionization

B401/

B110LP/

B116LP

A

0.12

15/15/1

System Sensor 2151

A

Photoelectric

B401/

B110LP/

B116LP

A

0.12

15/15/1

Advertising