Last event recall, Non-silenceable service, Sprinkler supervisory tracking – System Sensor PDRP-1001 User Manual

Page 34: System events

Advertising
background image

3. System Operation

Last Event Recall

34

PDRP-1001 Instruction Manual PN 50734:D0 04/06/01

Last Event Recall

Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes use
of the four panel switches as follows:

1. Press and hold in the TONE SILENCE switch.

2. With the TONE SILENCE switch held in, press (in sequence) the SYSTEM RESET switch, the

ALARM ACTIVATE switch, and then the ALARM SILENCE switch.

3. LEDs will light to indicate the last event recorded in the panel’s buffer.

4. Release the TONE SILENCE switch to return to normal operation.

To clear the Last Event buffer, press SYSTEM RESET twice.

Non-Silenceable Service

Notification Appliance Circuit #1 can be programmed as non-silenceable by following these steps:

1. Press and hold in the TONE SILENCE switch.

2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then

the ALARM ACTIVATE switch, and finally the ALARM SILENCE switch again.

3. Release the TONE SILENCE switch.

Note: If both primary and secondary power sources are removed from the system, these settings will be lost. When
power is restored, Notification Appliance Circuit #1 will default to silenceable operation.

Sprinkler Supervisory Tracking

The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation;
latching operation is the default setting. Canadian regulations require latching operation.

1. Press and hold in the TONE SILENCE switch.

2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then

the ALARM ACTIVATE switch, and finally the ALARM ACTIVATE switch again.

3. Release the TONE SILENCE switch.

Note: If both primary and secondary power sources are removed from the system, this setting will be lost. When
power is restored, supervisory will default to latching operation.

System Events

Standby Condition

Green LED (AC power on) will be illuminated. All other LEDs (trouble and alarm) are off.

System Trouble Condition

Interruption of any of the electrically supervised circuits will illuminate the System Trouble LED. The
Trouble Relay Contacts will transfer. The piezo (local buzzer) will sound one second on, one second off,
and repeating until silenced. Silence the piezo by pressing the TONE SILENCE switch. The panel will
remain in the trouble state until the trouble condition has been cleared and the panel reset.