Setting Mode of Operation

2. Installation

PDRP-1001 Instruction Manual PN 50734:D0 04/06/01

29

Discharge Timer

Select the desired discharge timer setting by setting DIP Switches 3, 4 and 5 accordingly.

• For NFPA 13 and 15 applications timer must be set to “Disabled”.
• For NFPA 16 applications timer may be set to “10 Minutes” or “15 Minutes”.

Note: Timer will always start at Zone 2 normal to alarm transition. Upon timeout, corresponding release circuits will
shut off.

Note: Zone 1 will always override timer shutoff (except for Mode #4 - Split Release).

Disabled

10 Minutes

15 Minutes

Switch #3

OFF

ON

ON

Switch #4

OFF

ON

ON

Switch #5

OFF

OFF

ON