2. Installation

Power-Up Procedure

30

PDRP-1001 Instruction Manual PN 50734:D0 04/06/01

Power-Up Procedure

WARNING: Prior to energizing this panel, notify all personnel and authorities, including any
personnel who may be working on, around, or near this unit.

WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
water for 15 minutes and seek immediate medical attention.

CAUTION: Observe polarity of batteries. Improper connection will cause damage and VOID
WARRANTY.

Follow these steps to power-up the FACP:

1. Conduct Visual Inspection. A careful visual inspection should be made before applying power to

the system. See “Inspection” on page 51.

2. Notification. Notify personnel who may be working with the AC power circuits before removing

the “Out of Service” tag.

3. Apply Primary Power. Switch the circuit breaker to the ‘closed’ position, providing power to the

circuit.
• The green AC power LED will illuminate.
• The Trouble LED will illuminate until battery power is applied.

4. Connect Secondary Power. Connect battery interconnect wire as shown below.

• The trouble LED will clear. If the trouble light does not clear, refer to "Troubleshooting Table" on

page 52.

Figure 20 Battery Connections

!

!

M

S

44

-bat

cab

le

.cdr

Battery Interconnect Wire