Sterling AquaSnap 30RA010-055 User Manual

Page 19

Advertising
background image

19

Table 7 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve

*Minimum Load Valve energized.

NOTE: These capacity steps may vary due to different capacity
staging sequences.

30RA UNIT SIZE

CONTROL

STEPS

LOADING SEQ A

LOADING SEQ B

% Displacement

Compressor

% Displacement

Compressor

010 (50/60 Hz)

1
2

69/ 71

100/100

A1*

A1



015 (60 Hz)

1
2

79

100

A1*

A1



015 (50 Hz)

1
2
3

28
50

100

A1*

A1

A1,A2





018 (50/60 Hz)

1
2
3

32/ 31
50/ 50

100/100

A1*

A1

A1,A2





022 (50/60 Hz)

1
2
3

27/ 35
42/ 50

100/100

A1*

A1

A1,A2





025 (50/60 Hz)

1
2
3

38/ 37
50/ 50

100/100

A1*

A1

A1,A2





030

1
2
3

39
50

100

A1*

A1

A1,A2





032

1
2
3
4

15
25
60

100

A1*

A1

A1,A2

A1,A2,B1

30
40
65

100

B1*

B1

A1,B1

A1,A2,B1

035 (50/60 Hz)

1
2
3
4

16/25
25/33
60/67

100

A1*

A1

A1,A2

A1,A2,B1

32/25
40/33
65/67

100

B1*

B1

A1,B1

A1,A2,B1

040

1
2
3
4

24
32
63

100

A1*

A1

A1,A2

A1,A2,B1

29
37
68

100

B1*

B1

A1,B1

A1,A2,B1

042

1
2
3
4
5

18
25
50
75

100

A1*

A1

A1,B1

A1,A2,B1

A1,A2,B1,B2

18
25
50
75

100

B1*

B1

A1,B1

A1,B1,B2

A1,A2,B1,B2

045 (60 Hz)

1
2
3
4
5

15
22
44
72

100

A1*

A1

A1,B1

A1,A2,B1

A1,A2,B1,B2

15
22
44
72

100

B1*

B1

A1,B1

A1,B1,B2

A1,A2,B1,B2

045 (50 Hz), 050

1
2
3
4
5

19
25
50
77

100

A1*

A1

A1,B1

A1,A2,B1

A1,A2,B1,B2

19
25
50
77

100

B1*

B1

A1,B1

A1,B1,B2

A1,A2,B1,B2

055

1
2
3
4
5

20
25
50
75

100

A1*

A1

A1,B1

A1,A2,B1

A1,A2,B1,B2

20
25
50
75

100

B1*

B1

A1,B1

A1,B1,B2

A1,A2,B1,B2