Alarms and Alerts —

These are warnings of abnormal

or fault conditions, and may cause either one circuit or the
whole unit to shut down. They are assigned code numbers as
described in Table 29.

Automatic alarms will reset without operator intervention if

the condition corrects itself. The following method must be
used to reset manual alarms:

Before resetting any alarm, first determine the cause of the

alarm and correct it. Enter the Alarms mode indicated by the
LED on the side of the Scrolling Marquee Display. Press

and

until the sub-menu item RCRN “RESET

ALL CURRENT ALARMS” is displayed. Press

.

The control will prompt the user for a password, by displaying
PASS and WORD. Press

to display the default pass-

word, 1111. Press

for each character. If the password

has been changed, use the arrow keys to change each individu-
al character. Toggle the display to “YES” and press

.

The alarms will be reset.

Table 29 — Alarm and Alert Codes

ENTER

ENTER

ENTER

ENTER

ENTER

ALARM/

ALERT

CODE

ALARM

OR

ALERT

DESCRIPTION

WHY WAS THIS

ALARM

GENERATED?

ACTION TAKEN

BY CONTROL

RESET

METHOD

PROBABLE

CAUSE

T051

Alert

Circuit A, Compressor 1
Failure

Compressor feedback signal
does not match relay state

Compressor A1 shut
down.

Manual

High-pressure switch open,
faulty auxiliary contacts, loss
of condenser air, liquid
valve closed, filter drier
plugged, non-condensables,
operation beyond capability.

T052

Alert

Circuit A, Compressor 2
Failure

Compressor feedback signal
does not match relay state

Compressor A2 shut
down.

Manual

High-pressure switch open,
faulty auxiliary contacts, loss
of condenser air, liquid
valve closed, filter drier
plugged, non-condensables,
operation beyond capability.

T055

Alert

Circuit B, Compressor 1
Failure

Compressor feedback signal
does not match relay state

Compressor B1 shut
down.

Manual

High-pressure switch open,
faulty auxiliary contacts, loss
of condenser air, liquid
valve closed, filter drier
plugged, non-condensables,
operation beyond capability.

T056

Alert

Circuit B, Compressor 2
Failure

Compressor feedback signal
does not match relay state

Compressor B2 shut
down.

Manual

High-pressure switch open,
faulty auxiliary contacts, loss
of condenser air, liquid
valve closed, filter drier
plugged, non-condensables,
operation beyond capability.

A060

Alarm

Cooler Leaving Fluid
Thermistor Failure (T1)

Thermistor outside range of
–40 to 245 F (–40 to 118 C)

Chiller shutdown
immediately

Automatic Thermistor failure, damaged

cable/wire or wiring error.

A061

Alarm

Cooler Entering Fluid
Thermistor Failure (T2)

Thermistor outside range of
–40 to 245 F (–40 to 118 C)

Chiller shutdown
immediately

Automatic Thermistor failure, damaged

cable/wire or wiring error.

T068

None

Circuit A Return Gas Thermistor Failure

If return gas sensors are
enabled (RG.EN) and
thermistor is outside range of
–40 to 245 F (–40 to 118 C)

None

Automatic Thermistor failure, damaged

cable/wire or wiring error.

T069

None

Circuit B Return Gas Thermistor Failure

If return gas sensors are
enabled (RG.EN) and
thermistor is outside range of
–40 to 245 F –40 to 118 C)

None

Automatic Thermistor failure, damaged

cable/wire or wiring error.

T073

Alert

Outside Air Thermistor
Failure (T9)

Thermistor outside range of
–40 to 245 F (–40 to 118 C)

Temperature reset
disabled. Chiller runs
under normal control/set
points. When capacity
reaches 0, cooler/pump
heaters are energized.

Automatic Thermistor failure, damaged

cable/wire or wiring error.

T074

Alert

Space Temperature
Thermistor Failure (T10)

Thermistor outside range of
–40 to 245 F (–40 to 118 C)

Temperature reset
disabled. Chiller runs
under normal control/set
points.

Automatic Thermistor failure, damaged

cable/wire or wiring error.

T077

Alert

Circuit A Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature

Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor
(T1).

Circuit A shutdown after
pumpdown complete.

Automatic Faulty expansion valve or

suction pressure transducer
(T5) or leaving fluid
thermistor (T1).

T078

Alert

Circuit B Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature

Faulty expansion valve,
suction pressure transducer
or leaving fluid thermistor
(T1).

Circuit B shutdown after
pumpdown complete

Automatic Faulty expansion valve or

suction pressure transducer
(T6) or leaving fluid
thermistor (T1).

T079

Alert

Lead/Lag LWT
Thermistor Failure

Thermistor outside range of
–40 to 245 F (–40 to 118 C)

Chiller runs as a stand
alone machine

Automatic Dual LWT thermistor failure,

damaged cable/wire or
wiring error.

T090

Alert

Circuit A Discharge
Pressure Transducer Failure

Voltage ratio more than
99.9% or less than .5%.

Circuit A shut down

Automatic Transducer failure, poor

connection to MBB, or wiring
damage/error.

T091

Alert

Circuit B Discharge
Pressure Transducer Failure

Voltage ratio more than
99.9% or less than .5%.

Circuit B shut down

Automatic Transducer failure, poor

connection to MBB, or wiring
damage/error.

T092

Alert

Circuit A Suction
Pressure Transducer Failure

Voltage ratio more than
99.9% or less than .5%.

Circuit A shut down

Automatic Transducer failure, poor

connection to MBB, or wiring
damage/error.