Sterling AquaSnap 30RA010-055 User Manual

Page 80

Advertising
background image

80

OPTIONS1 (Options 1 Configuration)

OPTIONS2 (Options 2 Configuration)

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

Cooler Fluid

1 = Water
2 = Med. Brine

1

FLUIDTYP

Minimum Load Vlv Select

No/Yes

No

MLV_FLG

Return Gas Sensor Enable

Dsable/Enable

Dsable

RGT_ENA

Motormaster Select

No/Yes

No

MTR_TYPE

Cooler Pump Control

Off/On

Off

CPC

Cooler Pump 1 Enable

No/Yes

No

PMP1_ENA

Cooler Pump 2 Enable

Dsable/Enable

Dsable

PMP2_ENA

Cooler Pmp Periodic Strt

No/Yes

No

PUMP_PST

Cooler Pump Select

0 = Automatic
1 = Pump 1
2 = Pump 2

0

PMP_SLCT

Cooler Pump Shutdown Dly

0 to 10

1

minutes

PUMP_DLY

Pump Changeover Hours

10 to 2000

500

hours

PMP_DLTA

EMM Module Installed

No/Yes

No

EMM_BRD

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

Control Method

0 = Switch
2 = Occupancy
3 =

SCN

0

CONTROL

Loading Sequence Select

1 = Equal Loading
2 = Staged Loading

1

SEQ_TYP

Lead/Lag Circuit Select

0 = Automatic
1 = Circuit A Leads
2 = Circuit B Leads

0

LEAD_TYP

Cooling Setpoint Select

0 = Single
1 = Dual, remote switch controlled
2 = Dual

SCN occupancy

3 = 4-20 mA input

0

CLSP_TYP

Ramp Load Select

Enable/Dsable

Enable

RAMP_EBL

Heat Cool Select

Cool/Heat

Cool

HEATCOOL

High LCW Alert Limit

2 to 60

60.0

∆∆∆∆F

LCW_LMT

Minutes off time

0 to 15

0

min

DELAY

Deadband Multiplier

1.0 to 4.0

2.0

Z_GAIN

Ice Mode Enable

Enable/Dsable

Dsable

ICE_CNFG

Close Control Select

Enable/Dsable

Dsable

CLS_CTRL

Low Sound Mode Select

0 = Disabled
1 = Fan only
2 = Capacity/Fans

1

LS_MODE

Low Sound Start Time

00:00 to 23:59

00:00

LS_START

Low Sound End Time

00:00 to 23:59

00:00

LS_END

Low Sound Capacity Limit

0 to 100

100

%

LS_LIMIT

Enable Short Loop Gain

Enable/Dsable

Enable

SAGENABL