Table 17 — Configuration Mode and Sub-Mode Directory (cont)

SUB-MODE

KEYPAD

ENTRY

ITEM DISPLAY

ITEM

EXPANSION

COMMENT

RSET (cont)

RM.F

XXX.X

°F

REMOTE - FULL RESET TEMP

Default: 0.0

° F (-17.8 C)

Range: 0

° to 125 F

RM.DG

XX.X

°F

REMOTE - DEGREES RESET

Default: 0.0

° F

Range: –30 to 30

F

RT.NO

XXX.X

∆F

RETURN - NO RESET TEMP

Default: 10.0

∆F (5.6 ∆C)

Range: 0

° to 125 F COOLER ∆T

RT.F

XXX.X

∆F

RETURN - FULL RESET TEMP

Default: 0.0

∆F (0.0 ∆C)

Range: 0

° to 125 F COOLER ∆T

RT.DG

XX.X

°F

RETURN - DEGREES RESET

Default: 0.0

° F

Range: –30 to 30

F (–34.4 to -1.1 C)

DMDC

X

DEMAND LIMIT SELECT

Default: None
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 =

SCN Loadshed

DM20

XXX %

DEMAND LIMIT AT 20 MA

Default: 100%
Range: 0 to 100%

SHNM

XXX

LOADSHED GROUP NUMBER

Default: 0
Range: 0 to 99

SHDL

XXX %

LOADSHED DEMAND DELTA

Default: 0%
Range: 0 to 60%

SHTM

XXX

MAXIMUM LOADSHED TIME

Default: 60 minutes
Range: 0 to 120 minutes

DLS1

XXX %

DEMAND LIMIT SWITCH 1

Default: 80%
Range: 0 to 100%

DLS2

XXX %

DEMAND LIMIT SWITCH 2

Default: 50%
Range: 0 to 100%

LLEN

ENBL/DSBL

LEAD/LAG CHILLER ENABLE

Default: Disable

MSSL

SLVE/MAST

MASTER/SLAVE SELECT

Default: Master

SLVA

XXX

SLAVE ADDRESS

Default: 2
Range: 0 to 239

LLBL

X

LEAD/LAG BALANCE SELECT

Default: Master Leads
0 = Master Leads
1 = Slave Leads
2 = Automatic

LLBD

XXX

LEAD/LAG BALANCE DELTA

Default: 168 hours
Range: 40 to 400 hours

LLDY

XXX

LAG START DELAY

Default: 5 minutes
Range: 0 to 30 minutes

PARA

YES

PARALLEL CONFIGURATION

Default: YES (CANNOT BE CHANGED)

SLCT

SETPOINT AND RAMP LOAD

CLSP

X

COOLING SETPOINT SELECT

Default: Single
0 = Single
1 = Dual Switch
2 = Dual

SCN Occupied

3 = 4 to 20 mA Input (requires

EMM)

RL.S

ENBL/DSBL

RAMP LOAD SELECT

Default: Enable

CRMP

X.X

COOLING RAMP LOADING

Default: 1.0
Range: 0.2 to 2.0

SCHD

XX

SCHEDULE NUMBER

Default: 1
Range: 1 to 99

Z.GN

X.X

DEADBAND MULTIPLIER

Default: 2.0
Range: 1.0 to 4.0

SERV

SERVICE CONFIGURATION

EN.A1

ENBL/DSBL

ENABLE COMPRESSOR A1

Unit dependent

EN.A2

ENBL/DSBL

ENABLE COMPRESSOR A2

Unit dependent

EN.B1

ENBL/DSBL

ENABLE COMPRESSOR B1

Unit dependent

EN.B2

ENBL/DSBL

ENABLE COMPRESSOR B2

Unit dependent

BCST

BROADCAST CONFIGURATION

T.D.BC ON/OFF

SCN TIME/DATE BROADCAST

OAT.B ON/OFF

SCN OAT BROADCAST

G.S.BC ON/OFF GLOBAL SCHEDULE BROADCAST

BC.AK ON/OFF

SCN BROADCAST ACK’ER

ENTER

ENTER

ENTER

ENTER