III. Unit Start-Up (cont)

PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’.
PRESS ENTER KEY.

RECORD CONFIGURATION INFORMATION BELOW.

OPTIONS2 (Options Configuration)

RSET (Reset Configuration Settings)

SUBMODE

ITEM

DISPLAY

DESCRIPTION

VALUE

OPT2

UNIT OPTIONS 2 CONTROLS

CTRL

X

CONTROL METHOD

SCNA XXX SCN ADDRESS
SCNB XXX SCN BUS NUMBER

BAUD X

SCN BAUD RATE

LOAD

X

LOADING SEQUENCE SELECT

LLCS

X

LEAD/LAG CIRCUIT SELECT

LCWT

XX.X

∆F

HIGH LCW ALERT LIMIT

DELY

XX

MINUTES OFF TIME

ICE.M

ENBL/DSBL

ICE MODE ENABLE

CLS.C

ENBL/DSBL

CLOSE CONTROL SELECT

LS.MD

X

LOW SOUND MODE SELECT

LS.ST

00:00

LOW SOUND START TIME

LS.ND

00:00

LOW SOUND END TIME

LS.LT

XXX %

LOW SOUND CAPACITY LIMIT

SUBMODE

ITEM

DISPLAY

DESCRIPTION

VALUE

RSET

RESET COOL TEMP

CRST

X

COOLING RESET TYPE

MA.DG

XX.X °F

4-20 - DEGREES RESET

RM.NO

XXX.X °F

REMOTE - NO RESET TEMP

RM.F

XXX.X °F

REMOTE - FULL RESET TEMP

RM.DG

XX.X °F

REMOTE - DEGREES RESET

RT.NO

XXX.X °F

RETURN - NO RESET TEMP

RT.F

XXX.X °F

RETURN - FULL RESET TEMP

RT.DG

XX.X °F

RETURN - DEGREES RESET

DMDC

X

DEMAND LIMIT SELECT

DM20

XXX %

DEMAND LIMIT AT 20 MA

SHNM

XXX

LOADSHED GROUP NUMBER

SHDL

XXX %

LOADSHED DEMAND DELTA

SHTM

XXX

MAXIMUM LOADSHED TIME

DLS1

XXX %

DEMAND LIMIT SWITCH 1

DLS2

XXX %

DEMAND LIMIT SWITCH 2

LLEN

ENBL/DSBL

LEAD/LAG CHILLER ENABLE

MSSL

SLVE/MAST

MASTER/SLAVE SELECT

SLVA

XXX

SLAVE ADDRESS

LLBL

X

LEAD/LAG BALANCE SELECT

LLBD

XXX

LEAD/LAG BALANCE DELTA

LLDY

XXX

LAG START DELAY

PARA

YES/NO

PARALLEL CONFIGURATION