Table 22 — Dual Chiller Configuration (Slave Chiller Example)

NOTES:

1. Slave Control Method (CTRL) must be configured for 0.
2. Slave

SCN Address (SCNA) must be different than Master.

3. Slave

SCN Bus Number (SCNB) must be the same as Master

4. Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.

SUB-MODE

ITEM

KEYPAD ENTRY

DISPLAY

ITEM EXPANSION

COMMENTS

DISP

UNIT

OPT1

OPT2

CTRL

CONTROL METHOD

CTRL

0

SWITCH

DEFAULT 0

CTRL

CTRL

SCNA

SCNA 1 SCN ADDRESS SCROLLING STOPS

1 VALUE FLASHES

2

SELECT 2

(SEE NOTE 1)

SCNA 2 SCN ADDRESS CHANGE ACCEPTED

SCNA

SCNB

SCNB 0 SCN BUS NUMBER DEFAULT 0

(SEE NOTE 2)

SCNB

OPT2

RSET

PROCEED TO

SUBMODE RSET

RSET

CRST

COOLING RESET TYPE

LLEN

LEAD/LAG CHILLER ENABLE

15 ITEMS

LLEN

DSBL

SCROLLING STOPS

DSBL

VALUE FLASHES

ENBL

SELECT ENBL

LLEN

ENBL

LEAD/LAG CHILLER ENABLE

CHANGE ACCEPTED

LLEN

MSSL

MASTER /SLAVE SELECT

MSSL

MAST

SCROLLING STOPS

MAST

VALUE FLASHES

SLVE

SELECT SLVE

MSSL

SLVE

MASTER /SLAVE SELECT

CHANGE ACCEPTED

MSSL

RSET

SLAVE COMPLETE

ENTER

ESCAPE

ENTER

ENTER

ENTER

ESCAPE

ENTER

ESCAPE

ESCAPE

ENTER

ENTER

ENTER

ENTER

ESCAPE

ENTER

ENTER

ENTER

ESCAPE

ESCAPE