CURRMODS: Maintenance Display

DUALCHIL: Maintenance Display

DESCRIPTION

VALUE

POINT NAME

FSM controlling Chiller

On/Off

MODE_1

WSM controlling Chiller

On/Off

MODE_2

Master/Slave control

On/Off

MODE_3

Ramp Load Limited

On/Off

MODE_5

Timed Override in effect

On/Off

MODE_6

Low Cooler Suction TempA

On/Off

MODE_7

Low Cooler Suction TempB

On/Off

MODE_8

Slow Change Override

On/Off

MODE_9

Minimum OFF time active

On/Off

MODE_10

Dual Setpoint

On/Off

MODE_13

Temperature Reset

On/Off

MODE_14

Demand/Sound Limited

On/Off

MODE_15

Cooler Freeze Protection

On/Off

MODE_16

Low Temperature Cooling

On/Off

MODE_17

High Temperature Cooling

On/Off

MODE_18

Making ICE

On/Off

MODE_19

Storing ICE

On/Off

MODE_20

High SCT Circuit A

On/Off

MODE_21

High SCT Circuit B

On/Off

MODE_22

Minimum Comp. On Time

On/Off

MODE_23

Pump Off Delay Time

On/Off

MODE_24

Low Sound Mode

On/Off

MODE_25

Short Loop Override

On/Off

MODE_26

DESCRIPTION

VALUE

UNITS

POINT NAME

Dual Chiller Link Good?

Yes/No

DC_LINK

Master Chiller Role

Stand Alone,

Lead Chiller,

Lag Chiller

MC_ROLE

Slave Chiller Role

Stand Alone,

Lead Chiller,

Lag Chiller

SC_ROLE

Lead Chiller Ctrl Point

snnn.n

°°°°F

LEAD_CP

Lag Chiller Ctrl Point

snnn.n

°°°°F

LAG_CP

Control Point

snnn.n

°°°°F

CTRL_PNT

Cool EnteringFluid-Slave

snnn.n

°°°°F

COOLEWTS

Cool Leaving Fluid-Slave

snnn.n

°°°°F

COOLLWTS

Cooler Entering Fluid

snnn.n

°°°°F

COOL_EWT

Cooler Leaving Fluid

snnn.n

°°°°F

COOL_LWT

Lead/Lag Leaving Fluid

snnn.n

°°°°F

DUAL_LWT

Percent Avail.Capacity

0-100

%

CAP_A

Percent Avail.Cap.Slave

0-100

%

CAP_A_S

Lag Start Delay Time

hh:mm

LAGDELAY

Load/Unload Factor

snnn.n

SMZ

Load/Unload Factor-Slave

snnn.n

SMZSLAVE

Lead SMZ Clear Commanded

Yes/No

LEADSMZC

Lag- SMZ Clear Commanded

Yes/No

LAG_SMZC

Lag Commanded Off?

Yes/No

LAG_OFF

Dual Chill Lead CapLimit

0-100

%

DCLDCAPL

Dual Chill Lag CapLimit

0-100

%

DCLGCAPL

Advertising