3 country-specific parameter settings, Country-specific parameter settings – SMC Networks Sunny Mini Central SMC 5000A User Manual

Page 89

Advertising
background image

SMA

Technologie AG

Technical Data

Installation Guide

SMC50A_60A-IEN073320

Page 89

14.4.3 Country-specific Parameter Settings

Sunny Mini Central SMC 5000A

The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in section 14.4.2.

Parameters designated with * are safety-related grid monitoring parameters. To
change the SMA grid guard parameters, you must enter your personal SMA grid
guard password (Inst.-Code). Call the SMA Serviceline to obtain your personal
SMA grid guard password.

You can see the default settings of the Sunny Mini Central on the name plate (see
section 4.1 "Identification" (Page 12))
.

Name

Short

descr.

Country settings

Germany

Australia

Great

Britain

Italy

Spain

ACVtgRPro

V

253

253

253

253

253

Default

GER/

VDE0126-1-1

AUS/

AS4777

GB/

G83

IT/

DK5950

SP/

RD1663

dFac-Max

Hz/s

4

0,25

0.2

0.20

2

dZac-Max mOhm

685

20000

350

350

350

Fac-delta-

Hz

2,45

0,19

0.5

0.29

0.98

Fac-delta+

Hz

0,19

0,19

0.5

0.29

0.98

I-Ni-Test

mA

16000

8000

0

0

0

LDVtgC

V

0

50

50

50

50

T-Start

s

10

45

180

10

10

Uac-Min

V

198

205

209

198

199

Uac-Max

V

260

265

261

262

250