Manual of functions of remote controller and operation method

Manual 1 of functions of remote controller

6.1.1 Temperature parameter

The room setting temperature(Tpreset)

The room ambient temperature (Tamb)

6.1.2

Basic Functions

Once energized, the compressor should in no way be restarted unless after 3-minute time interval at least. For the first
energization, the compressor will be started without 3-minute lag.

The compressor, once started,will not be stopped

within

6 minutes with the change of room temperature.

Cooling Mode

Cooling Conditions and Process

When T

amb

.≥T

preset

+1℃, the unit will run under cooling mode, in which case the compressor and outdoor fan will start

and the indoor fan will run at set

ting speed.

When T

amb.

≤T

preset

-1℃, the compressor and the outdoor fan will stop, the indoor fan will run at setting speed.

When T

preset

-1 <T

amb.

< T

preset

+1 , the unit will maintain its original operating status.

Under this mode, the switchover valve will

not be powered on, and the setting temperature range is16 ~30 .

T

preset

+1℃

T

preset

-1℃

Compressor

Outdoor fan

Indoor fan

Preset speed

Run

T

amb

Stop

Stop cooling

Start cooling

Original operating status

≥6

min.

3 min.

≥6

min.

6.1.2.1.3 Protection

Antifreeze Protection

If it is detected that the system is under antifreeze protection, the compressor and outdoor fan will be stopped,
and the indoor fan will run at setting speed. When antifreeze protection is released and the compressor has stopped
for 3 minutes, the unit will resume its original operating status.

During antifreeze protection

3 min.

Stop

Run

Preset speed

Compressor

Outdoor fan

Indoor fan

6.1.2.2 DRY Modes

6.1.2.2 .1 The conditions and process of DRY

+2 , the unit will run under DRY cooling mode, in which case the compressor and outdoor fan

will be started and the indoor fan will run at low speed.

When T

amb.

> T

preset

When T

preset

-2℃≤T

amb.

T

preset

+2℃, the unit will run under DRY mode, in which case the indoor fan will keep run

at low speed, the compressor and the outdoor fan will be stopped after 6 minutes . After 4 minutes,the compressor
and the outdoor fan will be restarted. The dehumidifying process is so repeated in cycle.

.

When T

amb

.< T

preset

-2℃, the compressor and outdoor fan will be stopped, the indoor fan will run at low speed.

Under this mode, the switchover valve will

not be powered on, and the setting temperature range is16 ~30 .