3 protection, 3 conditions and processes of defrost, 4 protection – Sinclair KING ASH-09AK User Manual

Page 11: 4 fan mode, 5 auto mode

Advertising
background image

T

preset

+2℃

T

preset

-2℃

T

amb

Compressor

Outdoor fan

Indoor fan

Cooling

Dry

Stop

6 min

.

6 min

.

4

min.

4

min.

low

speed

Run

Stop

6.1.2.2.3 Protection

Antifreeze Protection

Upon meeting the cooling condition, i

f it is detected that the system is under antifreeze protection, the compressor

and outdoor fan will be stopped,

and the indoor fan will run at low speed. When antifreeze protection is released and

the compressor has stopped

for 3 minutes, the complete unit will resume its original operating status.

Upon meeting the dehumidify condition, i

f it is detected that the system is under antifreeze protection, the com

-pressor and outdoor fan will be stopped,

and the indoor fan will run at low speed. When antifreeze protection is released

and the compressor has stopped

for 4 minutes, the complete unit will resume its original operating status.

6.1.2.3 HEAT Mode (there is no this mode for cooling only unit)

6.1.2.3 .1The conditions and process of heating

Tset

Tset

Compressor

Outer fan

Inner fan

Reversal valve

Running

Stop

Stop heating

Original running state

Start heating

Tamb.

6Min.

3Min.

6Min.

2Min.

Setting
fan speed

2Min.

Setting
fan speed

When Tamb Tset +2 ,the system enters heating running, in this case, the reversal valve, compressor,

outer fan enter simultaneously running.The indoor fan will delay at most for 2min to run.

When Tamb Tset +4 ,the compressor and outdoor fan will stop, but the reversal valve is still with power on,

the indoor unit will run at setting fan speed for 60s then will stop .

When Tset +2 <Tamb < Tset +4 ,the unit will maintain its original operating status.

Under this mode, the switchover valve will

be powered on, and the setting temperature range is16 ~30 .

6.1.2.3.3 Conditions and processes of defrost

This unit adopt intelligent defrosting,it can defrost according to the frosting conditions,dual 8 display H1

6.1.2.3.4 Protection

High Temp. Protection

If it is detected that the evaporator tube temperature is too high, the outdoor fan will be stopped. When the tube
temperature resumes to normal, the outdoor fan will be restarted.

Noise Silencing Protection: If the unit is stopped by pressing ON/OFF, the reversal valve will be stopped after

2-minute lag; or 2 minutes will be delayed upon mode switching.

6.1.2.4 Fan mode

Under FAN mode, only the indoor fan runs at setting speed.The RUN indicator will be bright. Double 8 module indicator

will display the setting temperature. When stand by, the power indicator is bright but the unit does not run.

6.1.2.5 Auto Mode

Under this mode, the system will automatically select its run mode (cool, dehumidify, heat or fan) with the change of
ambient temperature. For protection function, same as under cooling and heating mode.