State Industries Premier Power Vent DV Series GP6 50 HTPDT 121 Series User Manual

Page 18

Advertising
background image

18

Gas pIpInG

Make sure gas supplied is same type listed on model rating plate.

The inlet gas pressure must not exceed 14 inch water column (3.5

kPa) for natural and propane gas (L.P.). The minimum inlet gas

pressure shown on rating plate is that which will permit firing at

rated input.

All gas piping must comply with local codes and ordinances or with the

National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper or brass

tubing and fittings (except tin lined copper tubing) shall not be

used.

If the gas control valve is subjected to pressures exceeding 1/2 psi

(3.5 kPa), the damage to the gas control valve could result in a fire

or explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used, also

turn “off” the gas at each appliance. Leave all gas appliances shut

“off” until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater.

Consult the current edition of National Fuel Gas Code

(ANSI Z223.1/NFPA 54) and your gas supplier concerning pipe

size.

There must be:

• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip leg (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control

valve.

• A flexible gas connector or a ground joint union between the shut

off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

condensate pIpInG

This water heater is a condensing unit and requires a drain to be

located in close proximity to allow the condensate to drain safely.

The condensate drains from the unit at the exhaust tee located at

the bottom of the unit (see figure 12). Condensate from this water

heater is mildly acidic. Please note that some local codes require

that condensate is treated by using a pH neutralizing filter prior to

disposal.

Caution must be used to ensure that the drain is free and clear of

debris and will not allow backflow through the condensate hose.

Consideration must be given to avoid freezing of the condensate

lines which could result in excessive build up of condensate inside

the water heater. Waterproof heat tape may be required to prevent

freezing of the condensate lines. Please ensure that the outlet of the

condensate drain does not create a slippery condition which could

lead to personal injury.

CONDENSATION WARNING: THIS WATER HEATER IS A

CONDENSING UNIT AND REQUIRES A DRAIN TO BE LOCATED

IN CLOSE PROXIMITY TO ALLOW CONDENSATE TO DRAIN

SAFELY. THE CONDENSATE DRAINS FROM UNIT AT THE

EXHAUST ELBOW LOCATED AT BOTTOM OF UNIT. NOTE:

IT IS IMPORTANT THAT THE CONDENSATE HOSE NOT BE

ELEvATED ABOvE THE EXHAUST ELBOW, SEE FIGURE 12.

CONDENSATE BUILD-UP WILL BLOCk THE EXHAUST OUTLET,

WHICH WILL CAUSE IMPROPER OPERATION.

fIGure 12

the condensate drain line must be routed to a suitable drain. If

no floor drain is available or the drain is above the level of the

condensate line, install a condensate pump that is resistant

to the acidic condensate. these pumps are available from

local distributors. If the pump is not resistant to acidic water,

a condensate neutralizer must be used ahead of the pump.

when installing the drain line, note the following:

• Plastic pipe or tubing must be used to connect the condensate

drain to a suitable drain or condensate pump. Do not use copper

tubing, iron, or steel pipe for the condensate drain line.

• Condensate drain lines should be installed in conditioned

areas only. Drain lines installed in areas that are subject to

freezing temperatures should be wrapped with a nationally

recognized/listed heat tape and/or approved insulation for

freeze protection. Install per manufacturer’s instructions.

• Do not common drain with the temperature and pressure relief

valve or the condensate line from an air conditioner evaporator

coil.

• Slope the condensate drain toward the inside floor drain or

condensate pump.

• The condensate drain line and connection to the drain piping

must comply with all local codes.

Advertising