Direct vent diagram – State Industries Premier Power Vent DV Series GP6 50 HTPDT 121 Series User Manual

Page 30

Advertising
background image

30

12” MINIMUM CLEARANCE ABOVE HIGHEST

ANTICIPATED SNOW LEVEL

12” MINIMUM CLEARANCE

ABOVE HIGHEST ANTICIPATED

SNOW LEVEL

24” MINIMUM SEPARATION. EXHAUST

MUST BE AT SAME LEVEL OR ABOVE

INTAKE TERMINAL.

dIrect vent dIaGraM

fIGure 28.

fIGure 30.

fIGure 31.

fIGure 32.

fIGure 29.

When direct venting through the wall, as shown in Figure 32, the

exhaust should terminate a minimum of 24” from the air intake. The

exhaust may be rotated up to 45 degrees left or right as long as the

24” distance is maintained.

The air intake screen can be removed for space heating at cold climate

installation to prevent potential air intake freeze up. If air intake screen

is removed during winter to prevent freezing it is recommended to re-

install the screen during non-space heating seasons.

If necessary to achieve the 12” minimum clearance above the highest

anticipated snow level or grade for the air intake install a snorkel,

similar to the exhaust, in the up position. Maintain the 24” distance

between the intake and exhaust terminations.

Optional cold climate sidewall direct vent kits are available: 318221-

000 for 2” vent systems and 318222-000 for 3” vent systems.