State Industries Premier Power Vent DV Series GP6 50 HTPDT 121 Series User Manual

Page 25

Advertising
background image

25

sequence of InstallatIons, fIGure 15a

Cut a length of PVC pipe about 3.5 inches (8.9 cm) longer than the

wall thickness at the opening. Glue the vent terminal to this section of

pipe. Slide the wall plate over the pipe to stop against the vent terminal.

Place a bead of caulking (not supplied) around the gap between the

pipe and cover plate. Apply enough to fill some of the gap between

the pipe and wall. Place some of the caulking on the back of the plate

to hold it against the wall after installation. If the vent pipe is installed

up to the wall, with a coupling on the end against the wall opening, the

pipe with the vent terminal can be prepared for gluing before inserting

through the wall. Slide the pipe through the wall and insert into the

coupling on the other side of the wall, making sure that the vent terminal

ends up pointed in the correct position, see Figure 15A.

vent terMInatIon - fIGure 15a

dIrect vent terMInal InstallatIon

The air intake provided on the unit contains a mesh screen to prevent

large particles from entering the unit.

fIGure 15b

WHEN THE UNIT IS TO BE SETUP AS A DIRECT vENT, THE

MESH SCREEN MUST BE REMOvED. THE INLET vENT PIPE

MAY THEN BE GLUED TO THE AIR INTAKE (See Figure 15B)

PROvIDED ON THE UNIT.

THIS UNIT CONSISTS OF TWO vENT TERMINALS - AN INTAkE

vENT TERMINAL AND AN EXHAUST vENT TERMINAL. THE INTAkE

VENT TERMINAL IS A 2” 90° PVC ELBOW(-) WITH A MESH WIRE

SCREEN AND THE EXHAUST VENT TERMINAL IS A 2” 22.5° PVC

COUPLING WITH A MESH WIRE SCREEN.

NOTE: TO PREVENT EXHAUSTING PRODUCTS FROM

CIRCULATING TO THE AIR INTAkE IN WINDY/COLD AREAS,

THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO

TERMINALS IS RECOMMENDED.

fIGure 15c

InstallatIon sequence

vent terMInals supplIed wIth heater Must be used.

NOTE: BEFORE BEGINNING INSTALLATION OF ANY

VENT PIPE READ THE VENT PIPE MANUFACTURER’S

INSTALLATION INSTRUCTIONS.

1. After the points of termination have been determined,

use the cover plates as templates to mark the holes for

the vent pipes to be inserted through the wall. BEWARE OF

CONCEALED WIRING AND PIPING INSIDE OF WALL. If the

vent terminals are being installed on the outside of a finished

wall, it may be easier to mark both the inside and outside

wall. Align the holesby drilling a hole through the center of the

template from the inside through to the outside. The template

can now be positioned on the outside wall using the drilled holes

as a centering point for the template.

A.) MASONRY SIDE WALLS Chisel an opening approximately

1/2” (1.3 cm) larger than the marked circle.

B.) WOODEN SIDE WALLS Drill a pilot hole approximately

one quarter inch outside of the marked circle. This

pilot hole is used as a starting point for a saws-all or

sabre saw blade. Cut around the marked circle staying

approximately one quarter inch outside of the line.

(This will allow the vent pipe to easily slide through

the opening. The resulting gap will be covered by the

vent terminal cover plates.) Repeat this step on the

inside wall if necessary.

2. Cut a length of 3” PVC pipe about 3.5” (8.9 cm) longer than the

wall thickness at the opening.

3. Glue the intake vent terminal to the section of the pipe.

4. Slide the wall plate over pipe to stop against intake vent terminal.

5. Place a bead of caulking (not supplied) around the gap between

the pipe and the wall. Place some of the caulking on the

back of the plate to hold it against the wall after installation.

6. If the vent pipe is installed up to the wall, with a coupling on the

end against the wall opening, the pipe with the vent terminal can

be prepared for gluing before inserting through the wall. Slide the

pipe through the wall and insert into coupling on the other side of

the wall, making sure that the vent terminal ends up pointed in the

correct position (Figure 15C and 16).

fIGure 16

Advertising