6. Installation

CAUTION

When installing the UPS, carefully follow the instructions in this Instruction Manual.

Install the UPS on a stable surface that can bear the weight (16 kg, 35.27 lbs).

This surface should be flat, so the UPS cannot fall and cause bodily injury.

The possibility of vibration and shock should be minimized at the installation location.

All work that involves lifting the UPS, such as mounting it in a rack or attaching the

stand, should be carried out by at least 2 persons.

Be careful to avoid straining your lower back when moving and installing the UPS.

There is a danger that the UPS could fall or be dropped during relocation or
installation. Always hold the UPS securely by the upper edges. Failure to do so can

result in bodily injury or damage to the UPS.

6.1 Environment

Do not install the UPS in the following locations:

• Where the ambient temperature exceeds 40°C (104°F).

For optimum battery life, install the UPS where the ambient temperature remains
between 20 to 25

°

C (68 to 77

°

F).

• Where high humidity may occur.
• Where corrosive gas or salt spray may be present.
• Where it may be subject to vibration and shock.

• Where dust may accumulate.
• In a poorly ventilated rack (when the UPS is rack mounted).

6.2 Transporting

Transport the UPS in its original packing
carton, removing it only when near the
installation location.

6.3 Installation Space

During installation, provide the following space around the UPS.

• At least 20 cm (about 8 inches) at the front as air intake space for cooling.
• At least 20 cm (about 8 inches) at the back as air exhaust space for cooling
• At least 1 meter (about 40 inches) at the front and 50 cm (about 20 inches) at the back

for maintenance when needed.

• At least 1 meter (about 40 inches) from CRT displays to allow for slight leakage of

magnetic flux. Allow some space from devices which might be affected by magnetic
flux.

Installation Space for Horizontal Installation Installation Space for Rack Mounting

Intake space

E11A

Exhaust space

At least 20cm

(Back)

(Front)

Rack

Maintenance space

At least 1m (40 in)

Maintenance space

At least 50 cm (20 in)

At least 20cm

(8 in)

(8 in)

Exhaust spac

At least

20cm (8 in)

At least 1m (40 in)

At least

20cm (8 in)

Intake space

Maintenance space

At least 50 cm (20 in)

Maintenance space

E11A

(Back)

Front

Exhaust space

CAUTION

When moving the UPS, do not let it tilt

more than 10 degrees to either side.

Tilting of more than 10 degrees can

cause the UPS to fall, resulting in

bodily injury.

If you must tilt the UPS more than 10

degrees, be careful not to let it fall.