6 battery exchange, Caution – Sanyo SANUPS E11A102A User Manual

Page 31

Advertising
background image

− 28 −

11.6 Battery Exchange

You can exchange the batteries without stopping the load devices. However, this should be
done as quickly as possible, because the UPS will be unable to provide backup power in the
event of a power outage.

CAUTION

The battery pack weighs about 6kg (13.23 lbs). Be careful not to drop it on
your feet. Bodily injury can result.

Wear insulated gloves and take other precautions when exchanging the
batteries. Otherwise electric shock can result.

There is a constant voltage (max. approx. 24V: approx. 12V

× 2) at the

battery terminals. Do not touch them with your hands or short circuit them.
Bodily injury can result.

Remove the front panel of the UPS.

Remove the screw on the right side of the battery cover, and then remove the battery

cover.

Disconnect the battery connector.

Pull the battery pack out.
















Insert the new battery pack so that the connector faces forward.

Connect the battery connector.



CAUTION

The battery connector cannot be inserted in
the wrong orientation. If it does not go in, do

not try to force it. Doing so can damage the

connector and result in electric shock.

Be careful not to get your hands caught when
securing the cover.

Remove by sliding in the

direction of the arrow while

firmly pressing the two

locations indicated by ●

Battery connector.

Insulate with tape or

other insulator.

Insert the battery pack

in the direction of the

arrow.

The connector cannot be

inserted in the wrong

orientation. Push in

until you hear a click.

Remove 1 screw*, and remove

the battery cover by sliding in

the direction of the arrow.

When a screw is used,
do not lose the removed screw.

When a non-dropping screw is used,

this screw cannot be removed from

the battery cover. Do not try to

detach it forcedly.

*Note for removing the screw

Advertising