Alarm sounds – Sanyo SANUPS E11A102A User Manual

Page 36

Advertising
background image

− 33 −

13. Alarm Sounds

The alarm buzzer emits sound patterns to alert you to failures and error conditions in the
UPS. Check the sound pattern and refer to the following table to for the steps to take.

Sound Pattern

UPS Status

What to Do

This is a mechanical

failure.

Contact your supplier.

During bypass operation
The bypass fuse is blown.

Exchange the fuse for the supplied fuse.
See §11.7 “Bypass Fuse Exchange”.

Continuous tone

The battery is exhausted.

The UPS will restart automatically when

utility power is restored.

Power is being supplied

from the battery because of

an input voltage or

frequency error.

Input the correct voltage or frequency.

The input switch

MAIN SW was set to

“OFF” during inverter

power supply.

Set the input switch MAIN SW to
“ON”.

2 seconds


**

** **...

2 beeps 2 beeps 2 beeps

The UPS is performing a

battery check.

Wait for the battery check to end.
You can stop the battery check by

pushing

and holding it for

1 second.

Continuous beeps
********

...

The battery voltage is low.

Input the correct voltage or frequency.
Set the input switch MAIN SW to
“ON”.

1 second 2 seconds


****

****

****

...

The load devices connected

to the output exceed the

rated capacity.

Connected fewer load devices to the

output.

2 seconds


*******

*******

7 beeps 7 beeps

The battery check result

was an error.

The battery must be exchanged.

Contact your supplier.

The battery has reached

half of its service life. The

red BATT.LOW indicator
lights.

A battery exchange is recommended.

Contact your supplier.

You can press

to stop the buzzer

sound.

2 seconds


*****

*****

...

5 beeps 5 beeps

The battery has reached its

service life.
The red BATT.LOW

indicator blinks.

The battery must be exchanged.

Contact your supplier.

You can press

to stop the buzzer

sound and red BATT.LOW blinking, but

they will start again the next time the

UPS is powered on.
This will continue until you exchange the

battery.

Note : Contact your supplier if any other failure occurs in the UPS.

Press

to stop the buzzer sound.