4 specifications – Sanyo SANUPS E11A102A User Manual

Page 42

Advertising
background image

− 39 −

15.4 Specifications

Item

Standard or Performance

Notes

Output capacity

1kVA/0.7kW

Cooling system

Forced air cooling

Phases

Single phase, 2-wire

Voltage

100,110,115,120V

-20% to +15% Double Conversion mode operation

±5% Economy /Active Filter mode operation

±10% Economy mode setting

User settable

(Rated voltage same as output voltage)

Frequency

50Hz or 60Hz

±8%: Double Conversion mode operation

±1, 3, 5%: Economy /Active Filter mode
operation

Power requirements

0.9kVA

Max. capacity during battery charging

AC in

pu

t

Input power factor

0.95 or more

During rated output (*2)

Phases

Single phase, 2-wire

Voltage

100, 110, 115, 120V

User settable

Voltage regulation

Rated voltage

±2%

Rated frequency

50Hz or 60Hz

Same as input frequency

(auto selection)

Frequency regulation

Rated frequency

±1%: Double Conversion mode Setting

Rated frequency

±1, 3, 5%: Economy/Active Filter

mode operation

1, 3, 5% selectable

Internal oscillator accuracy

±0.5%

Voltage waveform

Sine wave

Distortion factor of

voltage waveform

Linear load: 3% or less

100% rectifier load: 7% or less

During rated output

Rapid load

change

0%

⇔ 100% at transient or output

switch

Power outage,

recovery

Rated voltage

±5 %

During rated output

Transient

voltage

variation

Rapid input

voltage change

±10% variation

Response time

5 cycles or less

Load power factor (lag)

0.7 (lag)

Variation range 0.7 (lag) to 1.0

Overcurrent protection

Auto switch to bypass circuit at 105% or more

With auto return function

Inverter 105%

200ms

200% 30

seconds

AC Ou

tpu

t

Overload

capability

Bypass

800% 2

cycles

Type

Small sealed lead battery

Rated capacity

10 A・h (equivalent)

20 hour ratio

Number

2 (12V per battery)

2 in direct series

Batte

ri

es

Backup time

5 minutes (700W) 10 minutes (500W)

At 25°C (77°F) ambient temperature,
rated load

Generated heat

50W

Input leakage current

3mA or less

Operating environment

Ambient temperature: 0 to 40°C (32 to 104°F)

Relative humidity: 20 to 90%

(*3)

Acoustic noise

40 dB or less

1 m (approx. 40 inches) from UPS front

panel, 'A' characteristics (linear load)

(*1): The inverter is capable of operation synchronized with AC input and instantaneous

switchover provided that the AC input frequency is within

±3% (or 1%, 3%, 5%,

selectable) of the rated frequency, and the AC input voltage is within +15% to-20% of the
rated voltage.
The UPS enters battery operation with the AC input frequency is outside the specified
range.

(*2): When input voltage waveform distortion is under 1%.
(*3): The UPS contains batteries. Battery service life will be foreshortened if the UPS is used

in an environment where the ambient temperature exceeds 30°C (86°F).

(*4): If grounded, the ground phase of the input and output must match according to UPS

specifications.

(*5): The above table lists standard specifications. Some specifications are different for units

with long backup times. For details, refer to the external battery specification
instruction manual.