Minent

®

Operating / Troubleshooting

Batch size

In “batch” operating mode:
The batch size can by changed from the “batch size/remaining litres” display.
The S3Ca returns to the original continuous display a few seconds after the batch size has
been reset.

Priming

The “priming” function is activated by pressing both arrow keys at the same time (in “Stroke
rate” permanent display).

Cancel error

Error messages are cancelled by pressing the P key briefly.

Settings

mode

P

P

P

i

STOP

START

Continuous

display

2 s

Stop/start pump

Change directly alterable values

= Security lock (CODE 1)

= Security lock (CODE 2)

Prime

Start batch (in "batch" operating mode only)

Cancel error

Check adjustable values

2

2

1

1

8.2

Remote control

Remote control of the S2Ca is possible via a control cable or PROFIBUS

®

(see Section 5.3 and

Chapter 7, ”Supplementary instructions for ProMinent

®

gamma/ L and ProMinent

®

Sigma

versions with PROFIBUS

®

“ as well as your documentation in the annex).

9

Troubleshooting

WARNING

• EX-pump only: metering pumps and their peripheral equipment must be serviced by

specially trained or authorised personnel!

• Always take suitable precautions when using hazardous chemicals!

• Ensure the equipment is de-pressurised before working on the pump!

Pump primes despite completed stroke action and no venting

Cause

Crystalline deposits on the ball seat because valves have dried out.

Remedy

̈ Remove the suction sleeve from the chemical supply container and rinse out the liquid end

thoroughly.

̈ If still unsuccessful, dismantle valves and clean.

Fluid is seeping from the top plate

Cause

The liquid end is not sealed against the pump diaphragm.

Remedy

̈ Tighten screws in the liquid end.
̈ If unsuccessful, replace the diaphragm (see section 4.3).