Gas Error

Gas Error

Ensure that gas shut-off valve is open.

Check gas supply pressure. (There is an inlet pressure tap on the gas combination valve that can be

used for this purpose.) Supply pressure should be > 7" W.C. for natural gas or > 11" W.C. for propane.

Remove front lower panel and burner box cover. Turn unit on. Observe ignitors for first 101 seconds after

turning unit on. Ignitors should begin glowing and continue to glow for approximately 37 seconds.

(If the flame does not light on first attempt, this process will be repeated two additional times.)

Do

both ignitors

glow?

Does

one ignitor

glow?

Do both pilot

flames light (at least

temporarily)?

Place test leads

between terminal

TB-C2 and TB-C1.

Turn unit on. Check

voltage during first

30 seconds of

operation.

Test and replace

bad ignitor, as

required.

Check manifold pressure during first 30

seconds of operation. (There is a tap on the

gas combination valve for this purpose.)

Make sure that flame

sensors are

positioned at tip of

inner core of pilot

flame and are not

touching any metal

surface. Retry.

Is voltage

approximately 24

volts?

Replace RAM

module.

Replace both

ignitors.

Is manifold pressure approximately

4" W.C. for natural gas or approximately

10" W.C. for propane?

Replace gas valve.

Remove burner box. Remove pilot supply tube from pilot(s) not lighting.

Examine and replace pilot orifice if necessary. Replace pilot if damaged.

Ensure that ignitor is positioned properly relative to pilot. Adjust as necessary.

No

Yes

Yes

No

No

Yes

No

No

Yes

Done

Yes

No

Check and replace RAM

module and flame sensor,

as necessary.

Does main

burner come

on (with door

closed)?

Is voltage

approximately 24

volts?

Check and replace

RAM module, as

necessary.

Yes

No

Check voltage between

terminals P and C (or

PV and MVPV) on gas

valve during first 30

seconds of operation.

Yes