15

You can now adapt your installation to the source which it is

connected to.
Max. current of the AC source (power-sharing) {1107}.

In case of using the Xtender on a public grid, it is actually the value of the circuit
breaker on the source side (fuse or breaker).

In a building, this value lies generally between 8 and 16A.

In the case of a shorepower or of a camping terminal, it lies between 2 and 6A.

In case of using the Xtender on a genset, you can divide the genset power by the

operating voltage (for instance for a genset of 3500VA, or 3500W, and 230V you get
3500/230=15.2).

Caution: the powers given on the gensets are often overestimated compared to

their real performances. To obtain a useable value it is necessary to multiply this
result by 0.6 or 0.7 (in that case 15.2*0.7=10.64).

Press the key SET to modify the value of this parameter (it appears in reverse video). By means of
the keys “arrow upwards” and “arrow downwards” change the value to adapt it to your source

and validate your setting with the key SET (OK).

A

DAPTATION TO THE BATTERIE

Charge current {1138}

In order that your Xtender manages the best possible the energy stored in your batteries and that it

charges them optimally, it is necessary to indicate the current which they can be charged with.
You will find this value in the technical data provided by your batteries manufacturer.

In the case of lead-acid batteries, one generally uses one tenth or one fifth of the
battery capacity value.

For instance for a 500Ah battery: 500/10=50A to 500/5=100A.


The basic display is this one:

Press 3 times the key « arrow downwards » to display the

following screen:
If you go overpass this screen you can come back to it by

means of the key « arrow upwards »

Press the key SET to access to the settings.
With the key “arrow downwards”, access the menu “Battery

and charger cycle”.

Press the key SET to access this menu.


You are now going to set the charge current for the batteries:

Press the key SET to modify the value of this parameter (it

appears in reverse video). With the keys “arrow upwards” and
“arrow downwards” change the value to adapt your battery

and validate your setting with the key SET (OK).