Limit the time of activation {1512} {1513}

Maximum duration of activation {1514} {1515}

When the conditions are met, either one or two relays are activated permanently. If you wish that

the activation duration is limited in time, even if the conditions are met, you can activate this
function. Once the relay is activated, a countdown runs according to the duration you have

selected. Once this countdown is completed the relay is released, even if the conditions are still

there. The relay can not be anymore activated as long as the activation conditions have not disap-
peared.

Temporal restrictions {1203} {1312}

These configurations allow the time frame to be defined in which the contact should under no

circumstances be activated. Three distinct schedules are accessible in the form of restriction
programs (programs 1 to 3). For each program, it is possible to select the day of the week where

the restriction is activated. If the day is selected it appears on the screen and if it is not selected it is

represented on the screen by two horizontal lines.
Once the days are selected, it is necessary to adjust the time frame where the restriction is active

using the “starting time” and “finishing time” configurations. If the finishing time is programmed
before the starting time, the restriction time frame is not taken into account. Below are the

configurations with their references:
• Program 1 {1204} {1313}

o

Days of the week {1205} {1314}

o

Starting time {1206} {1315}

o

Finishing time {1207} {1316}

• Program 2 {1208} {1317}

o

Days of the week {1209} {1318}

o

Starting time {1210} {1319}

o

Finishing time {1211} {1320}

• Program 3 {1212} {1321}

o

Days of the week {1213} {1322}

o

Starting time {1214} {1323}

o

Finishing time {1215} {1324}

If your installer has made additional adjustments, it is possible that the restrictions

could be active even if they do not appear in one of the three programs available

to you.

Contacts activated by an event {1455} {1456}

The auxiliary contacts may be activated by the states or events occurring in the installation. Each

event may be combined with another to establish complex functions.

Xtender OFF {1225} {1333}
The contact is activated if the Xtender inverter/charger is switched off, either following a fault or

manually.

Battery undervoltage alarm {1226} {1334}
If the undervoltage threshold is reached, this activates the contact. In contrast to the acoustic

alarm that is deactivated after a set time, this signal remains active as long as the battery voltage is

below the threshold. If the undervoltage fault cuts in, this condition remains active as does the
contact.

Battery overvoltage {1227) {1335}
Activates the contact in the event of battery overvoltage.